Schneider Electric Contactor, TeSys Deca, 4P(4NO), AC-1, 440V, 200A, 230V AC 50/60Hz coil, screw clamp terminals LC1D115004P7

Schneider Electric · Electrical Components · Contactors · France · se.com
Part Number
LC1D115004P7  ·  HS 8536.90
Schneider Electric Contactor, TeSys Deca, 4P(4NO), AC-1, 440V, 200A, 230V AC 50/60Hz coil, screw clamp terminals LC1D115004P7

Schneider Electric LC1D115004P7 — TeSys Deca contactor. AC-3 rated 3-pole contactor with modular auxiliary and coil options. Contactor 200AC1 4NO 230VAC.

Technical Specifications

Manufacturer part number (MPN)LC1D115004P7
EAN / GTIN3389110053074
HS code8536.90
Sales unitpcs
Package quantity18 pcs
Voltage230 V AC
Contact configuration4 NO
RangeTeSys
Range of productTeSys Deca
Product or component typeContactor
Device short nameLC1D
Contactor applicationResistive load
Utilisation categoryAC-3; AC-3e; AC-1; AC-4
Poles description4P
[Ue] rated operational voltagePower circuit: <= 1000 V AC 25...400 Hz; Power circuit: <= 460 V DC
[Ie] rated operational current200 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
[Uc] control circuit voltage230 V AC 50/60 Hz
Compatibility codeLC1D
Pole contact composition4 NO
Protective coverWith
[Ith] conventional free air thermal current200 A (at 60 °C) for power circuit
Irms rated making capacity1260 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity1100 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current250 A 40 °C - 10 min for power circuit; 550 A 40 °C - 1 min for power circuit; 950 A 40 °C - 10 s for power circuit; 1100 A 40 °C - 1 s for power circuit
Associated fuse rating250 A gG at <= 690 V coordination type 1 for power circuit; 200 A gG at <= 690 V coordination type 2 for power circuit
Average impedance0.6 mOhm - Ith 200 A 50 Hz for power circuit
Power dissipation per pole24 W AC-1
[Ui] rated insulation voltagePower circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Power circuit: 1000 V conforming to IEC 60947-4-1
Overvoltage categoryIII
Pollution degree3
[Uimp] rated impulse withstand voltage8 kV conforming to IEC 60947
Safety reliability levelB10d = 684932 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 10000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Mechanical durability8 Mcycles
Electrical durability0.8 Mcycles 200 A AC-1 at Ue <= 440 V
Control circuit typeAC at 50/60 Hz
Coil technologyBuilt-in bidirectional peak limiting diode suppressor
Control circuit voltage limits0.3...0.5 Uc (-40…70 °C):drop-out AC 50/60 Hz; 0.8...1.15 Uc (-40…55 °C):operational AC 50/60 Hz; 1...1.15 Uc (55…70 °C):operational AC 50/60 Hz
Inrush power in VA280…350 VA 60 Hz cos phi 0.8 (at 20 °C); 280…350 VA 50 Hz cos phi 0.8 (at 20 °C)
Hold-in power consumption in VA2…18 VA 60 Hz cos phi 0.3 (at 20 °C); 2…18 VA 50 Hz cos phi 0.3 (at 20 °C)
Heat dissipation3…8 W at 50/60 Hz
Operating time6...20 ms opening; 20...50 ms closing
Maximum operating rate2400 cyc/h at 60 °C
Connections - terminalsControl circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end; Control circuit: screw clamp terminals 1 1…2.5 mm² - cable stiffness: flexible with cable end; Control circuit: screw clamp terminals 1 1…2.5 mm² - cable stiffness: flexible without cable end; Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible without cable end; Control circuit: screw clamp terminals 1 1…2.5 mm² - cable stiffness: solid without cable end; Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: solid without cable end; Power circuit: connector 1 10…120 mm² - cable stiffness: flexible without cable end; Power circuit: connector 2 10…50 mm² - cable stiffness: flexible without cable end; Power circuit: connector 1 10…120 mm² - cable stiffness: flexible with cable end; Power circuit: connector 2 10…50 mm² - cable stiffness: flexible with cable end; Power circuit: connector 1 10…120 mm² - cable stiffness: solid without cable end; Power circuit: connector 2 10…50 mm² - cable stiffness: solid without cable end
Tightening torqueControl circuit: 1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm; Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2; Power circuit: 12 N.m - on connector hexagonal screw head 4 mm; Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
Mounting supportRail; Plate
StandardsCSA C22.2 No 14; EN 60947-4-1; EN 60947-5-1; IEC 60947-4-1; IEC 60947-5-1; UL 60947-4-1
Product certificationsUL; GOST; RINA; DNV; CSA; BV; LROS (Lloyds register of shipping); GL; CCC; UKCA
IP degree of protectionIP20 front face conforming to IEC 60529
Protective treatmentTH conforming to IEC 60068-2-30
Climatic withstandconforming to IACS E10 exposure to damp heat; conforming to IEC 60947-1 Annex Q category D exposure to damp heat
Permissible ambient air temperature around the device-40…60 °C; 60…70 °C with derating
Operating altitude0...3000 m
Fire resistance850 °C conforming to IEC 60695-2-1
Flame retardanceV1 conforming to UL 94
Mechanical robustnessVibrations contactor open (2 Gn, 5...300 Hz) ; Vibrations contactor closed (4 Gn, 5...300 Hz) ; Shocks contactor closed (15 Gn for 11 ms) ; Shocks contactor open (6 Gn for 11 ms)
Height158 mm
Width150 mm
Depth132 mm
Product weight2.86 kg
Warranty (in months)18