cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Schneider Electric TeSys D contactor - 4P(2 NO + 2 NC) - AC-1 <= 440 V 80 A 220 V AC 50/60 Hz coil LC1D65008M7

Schneider Electric · Electrical Components · Contactors · France · se.com
Part Number
LC1D65008M7  ·  HS 8536.90
Schneider Electric TeSys D contactor - 4P(2 NO + 2 NC) - AC-1 <= 440 V 80 A 220 V AC 50/60 Hz coil LC1D65008M7

Schneider Electric LC1D65008M7 — TeSys Deca contactor. AC-3 rated 3-pole contactor with modular auxiliary and coil options. Contactor 80AC1 2NO/2NC 220AC.

Technical Specifications

Manufacturer part number (MPN)LC1D65008M7
EAN / GTIN3389110231793
HS code8536.90
Sales unitpcs
Contact configuration2 NO / 2 NC
RangeTeSys
Range of productTeSys Deca
Product or component typeContactor
Device short nameLC1D
Contactor applicationResistive load
Utilisation categoryAC-1
Poles description4P
[Ue] rated operational voltagePower circuit: <= 690 V AC 25...400 Hz; Power circuit: <= 300 V DC
[Ie] rated operational current80 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
[Uc] control circuit voltage220 V AC 50/60 Hz
Compatibility codeLC1D
Pole contact composition2 NO + 2 NC
Protective coverWith
[Ith] conventional free air thermal current80 A (at 60 °C) for power circuit
Irms rated making capacity1000 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity1000 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current640 A 40 °C - 10 s for power circuit; 900 A 40 °C - 1 s for power circuit; 110 A 40 °C - 10 min for power circuit; 260 A 40 °C - 1 min for power circuit
Associated fuse rating125 A gG at <= 690 V coordination type 1 for power circuit; 125 A gG at <= 690 V coordination type 2 for power circuit
Average impedance1.5 mOhm - Ith 80 A 50 Hz for power circuit
Power dissipation per pole9.6 W AC-1
[Ui] rated insulation voltagePower circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Power circuit: 690 V conforming to IEC 60947-4-1
Overvoltage categoryIII
Pollution degree3
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947
Safety reliability levelB10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Mechanical durability6 Mcycles
Electrical durability1.4 Mcycles 80 A AC-1 at Ue <= 440 V
Control circuit typeAC at 50/60 Hz
Coil technologyWithout built-in suppressor module
Control circuit voltage limits0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz; 0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz; 0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz; 1...1.1 Uc (60…70 °C):operational AC 50/60 Hz
Inrush power in VA140 VA 60 Hz cos phi 0.75 (at 20 °C); 160 VA 50 Hz cos phi 0.75 (at 20 °C)
Hold-in power consumption in VA13 VA 60 Hz cos phi 0.3 (at 20 °C); 15 VA 50 Hz cos phi 0.3 (at 20 °C)
Heat dissipation4…5 W at 50/60 Hz
Operating time4...19 ms opening; 12...26 ms closing
Maximum operating rate3600 cyc/h at 60 °C
Connections - terminalsControl circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end; Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end; Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end; Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end; Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end; Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end; Power circuit: screw clamp terminals 1 1…35 mm² - cable stiffness: flexible without cable end; Power circuit: screw clamp terminals 2 1…25 mm² - cable stiffness: flexible without cable end; Power circuit: screw clamp terminals 1 1…35 mm² - cable stiffness: flexible with cable end; Power circuit: screw clamp terminals 2 1…25 mm² - cable stiffness: flexible with cable end; Power circuit: screw clamp terminals 1 1…35 mm² - cable stiffness: solid without cable end; Power circuit: screw clamp terminals 2 1…25 mm² - cable stiffness: solid without cable end
Tightening torqueControl circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm; Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2; Power circuit: 8 N.m - on screw clamp terminals - cable 25…35 mm² hexagonal screw head 4 mm; Power circuit: 5 N.m - on screw clamp terminals - cable 1…25 mm² hexagonal screw head 4 mm; Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
Mounting supportPlate; Rail
StandardsCSA C22.2 No 14; EN 60947-4-1; EN 60947-5-1; IEC 60947-4-1; IEC 60947-5-1; UL 60947-4-1
Product certificationsRINA; BV; CSA; UL; LROS (Lloyds register of shipping); CCC; DNV; GL; GOST
IP degree of protectionIP20 front face conforming to IEC 60529
Protective treatmentTH conforming to IEC 60068-2-30
Climatic withstandconforming to IACS E10 exposure to damp heat
Permissible ambient air temperature around the device-40…60 °C; 60…70 °C with derating
Operating altitude0...3000 m
Fire resistance850 °C conforming to IEC 60695-2-1
Flame retardanceV1 conforming to UL 94
Mechanical robustnessShocks contactor open (8 Gn for 11 ms) ; Shocks contactor closed (10 Gn for 11 ms) ; Vibrations contactor opened (2 Gn, 5...300 Hz) ; Vibrations contactor closed (3 Gn, 5...300 Hz)
Height127 mm
Width85 mm
Depth125 mm
Product weight1.45 kg
Number of Units in Package 11
Number of Units in Package 25
Country of originCZ
Warranty (in months)18

Properties

MOQ1

Cross-References

Attached Documents