| Manufacturer part number (MPN) | LR9D32 |
| EAN / GTIN | 3606485420950 |
| Sales unit | pcs |
| Package quantity | 30 pcs |
| Range | TeSys |
| Product name | TeSys LRD |
| Device short name | LR9D |
| Product or component type | Electronic thermal overload relay |
| Relay application | Motor protection |
| Product compatibility | LC1D09; LC1D25; LC1D32; LC1D38; LC1D12; LC1D18 |
| Thermal overload class | Class 5…30 |
| Thermal protection adjustment range | 6.4…32 A |
| Power consumption in W | 300 mW |
| Mounting support | Under contactor; Plate, with specific accessories; Rail, with specific accessories |
| [Ue] rated operational voltage | 690 V for power circuit; 660 V for signalling circuit |
| [Ui] rated insulation voltage | Power circuit: 1000 V; Signalling circuit: 690 V |
| Tripping threshold | 1.25 In conforming to IEC 60947-4-1 |
| Control type | Red push-button: stop and manual reset; White 2 microswitches: adjustable trip class; Red knob: automatic reset; Grey dial: full-load current adjustment |
| Time range | 1.5...4 min - automatic reset time |
| [Ith] conventional free air thermal current | 5 A for signalling circuit |
| Associated fuse rating | 5 A gG for signalling circuit; 5 A BS for signalling circuit |
| [Uimp] rated impulse withstand voltage | 6 kV |
| Phase failure sensitivity | Phase difference > 40% 3 s conforming to IEC 60947-4-1 |
| Electromagnetic compatibility | Surge withstand: 2 kV common mode conforming to IEC 61000-4-5; Resistance to electrostatic discharge: 8 kV conforming to IEC 61000-4-2; Immunity to radiated radio-electrical interference: 10 V/m conforming to IEC 61000-4-3; Immunity to fast transients: 2 kV conforming to IEC 61000-4-4 |
| Connections - terminals | Control circuit: screw clamp terminals 1 cable 2.5 mm² - cable stiffness: solid or flexible - without cable end; Power circuit: screw clamp terminals 1 cable 16 mm² - cable stiffness: solid or flexible - without cable end |
| Tightening torque | Control circuit: 0.8 N.m on screw clamp terminals; Power circuit: 3.1 N.m on screw clamp terminals |
| Height | 72.5 mm |
| Width | 45 mm |
| Depth | 79.9 mm |
| Product weight | 0.18 kg |
| Standards | EN/IEC 60947-4-1; EN/IEC 60947-5-1; UL 60947-4-1; UL 60947-5-1; CSA C22.2 No 60947-4-1; CSA C22.2 No 60947-5-1; GB/T 14048.4; GB/T 14048.5 |
| Product certifications | IECEE CB Scheme; UL; CSA; CCC |
| IP degree of protection | IP20 front face conforming to IEC 60529 |
| Ambient air temperature for operation | -25…70 °C conforming to IEC 60255-8 |
| Ambient air temperature for storage | -55…80 °C |
| Operating altitude | 2000 m without derating |
| Mechanical robustness | Vibrations 10...150 Hz: 6 Gn conforming to IEC 60068-2-6; Shocks 11 ms: 15 gn conforming to IEC 60068-2-7 |
| Dielectric strength | 6 kV 50 Hz conforming to IEC 60255-5 |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 5.000 cm |
| Package 1 Width | 7.000 cm |
| Package 1 Length | 9.000 cm |
| Package 1 Weight | 220.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 30 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 6.629 kg |
| Country of origin | CN |
| Warranty (in months) | 18 |
| Mounting method | Direct attachment/single positioning |
| External power supply required | No |
| Rated control supply voltage AC 50 Hz | 690 V |
| Rated control supply voltage AC 60 Hz | 690 V |
| Voltage type (operating voltage) | AC |
| Release class | Adjustable |
| Type of electrical connection of main circuit | Screw connection |
| Voltage type for actuating | AC |
| Reset function input | No |
| Reset function automatic | Yes |
| Reset function push-button | Yes |