| Manufacturer part number (MPN) | LRE02 |
| EAN / GTIN | 3606480329692 |
| Sales unit | pcs |
| Package quantity | 33 pcs |
| Range | Easy TeSys |
| Range of product | Easy TeSys Protect |
| Product or component type | Differential thermal overload relay |
| Device short name | LRE |
| Relay application | Motor protection |
| Phase failure sensitivity | Tripping current 130 % of Ir on two phase, the last one at 0 conforming to IEC 60947-4-1 |
| Colour | Grey (RAL 7011) |
| Product compatibility | LC1E06...38 |
| Network type | AC |
| Network frequency | 50...60 Hz |
| Mounting support | Under contactor; Plate, with specific accessories; Rail, with specific accessories |
| Thermal overload class | Class 10A conforming to IEC 60947-4-1 |
| Signalling function | Relay trip indicator |
| Thermal protection adjustment range | 0.16…0.25 A |
| Tripping threshold | 1.14 +/- 0.06 Ir conforming to IEC 60947-4-1 |
| Mechanical robustness | Shocks: 6 Gn for 11 ms conforming to IEC 60068-2-7; Vibrations: 3 GN conforming to IEC 60068-2-6 |
| Auxiliary contact composition | 1 NO + 1 NC |
| [Ith] conventional free air thermal current | 5 A for signalling circuit |
| [Ue] rated operational voltage | <= 690 V AC |
| Associated fuse rating | 2 A gG for power circuit; 0.5 A aM for power circuit; 5 A gG for signalling circuit |
| [Ui] rated insulation voltage | 690 V conforming to IEC 60947-4-1 |
| [Uimp] rated impulse withstand voltage | 6 kV |
| Local signalling | Trip indicator |
| Control type | Push-button red stop: ; Push-button green reset: |
| Temperature compensation | -20…60 °C |
| Connections - terminals | Power circuit: screw clamp terminals 1 1.5…6 mm² - cable stiffness: flexible without cable end; Power circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end; Power circuit: screw clamp terminals 1 1…6 mm² - cable stiffness: solid without cable end; Signalling circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible without cable end; Signalling circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end; Signalling circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: solid without cable end |
| Recommended tightening torque | Power circuit: 1.7 N.m - on screw clamp terminals; Signalling circuit: 1.7 N.m - on screw clamp terminals |
| Height | 44.5 mm |
| Width | 45 mm |
| Depth | 70 mm |
| Product weight | 0.13 kg |
| Standards | EN/IEC 60947-1; EN/IEC 60947-5-1; EN/IEC 60947-4-1; GB/T 14048.1; GB/T 14048.4; GB/T 14048.5; EN/IEC 60335-1:Clause 30.2; EN/IEC 60335-2-40:Annex JJ |
| Product certifications | CB Scheme; CCC; CE; EAC |
| Protective treatment | TH conforming to IEC 60068 |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Ambient air temperature for operation | -20…60 °C without derating conforming to IEC 60947-4-1; -20…70 °C with derating |
| Ambient air temperature for storage | -60…80 °C |
| Fire resistance | 850 °C conforming to IEC 60068-2-1 |
| Dielectric strength | 6 kV at 50 Hz conforming to IEC 60255-5 |
| Electromagnetic compatibility | Surge withstand: 6 kV conforming to IEC 60801-5 |
| Number of Units in Package 1 | 1 |
| Number of Units in Package 2 | 33 |
| Warranty (in months) | 18 |
| Mounting method | Direct attachment |
| Number of auxiliary contacts as normally open contact | 1 |
| Number of auxiliary contacts as normally closed contact | 1 |
| Release class | CLASS 10 A |
| Type of electrical connection of main circuit | Screw connection |
| Max. rated operation voltage Ue | 690 V |
| Adjustable current range | 0.16–0.25 A |
| Reset function input | No |
| Reset function automatic | No |
| Reset function push-button | Yes |
| Country of origin | China |