| Manufacturer part number (MPN) | RMCA61BD |
| EAN / GTIN | 3389110108880 |
| Sales unit | pcs |
| Package quantity | 33 pcs |
| Range of product | Harmony Analog |
| Product or component type | Voltage/current converter |
| Analogue input type | Current 0...1.5 A AC/DC 50/60 Hz; Current 0...15 A AC/DC 50/60 Hz; Current 0...5 A AC/DC 50/60 Hz |
| Analogue output type | Current 0...20 mA = 100 kOhm by cabling |
| Protection type | Reverse polarity protection on output; Short-circuit protection on output; Overvoltage protection on output (+/- 30 V) |
| abnormal analogue output voltage | -15...0 V no input or input wire broken |
| abnormal analogue output current | -30…0 mA, output selected 0...20 mA no input or input wire broken; 4…30 mA, output selected 4...20 mA no input or input wire broken |
| [Us] rated supply voltage | 24 V DC +/- 20 %, isolated |
| Current consumption | <= 70 mA for voltage output; <= 90 mA for current output |
| Local signalling | LED (green) for power ON |
| Tightening torque | 0.6…1.1 N.m |
| Marking | CE |
| Surge withstand | 0.5 kV during 1.2/50 µs conforming to IEC 61000-4-5 |
| [Ui] rated insulation voltage | 2 kV |
| Fixing mode | By screws (mounting plate); Clip-on (35 mm symmetrical DIN rail) |
| Safety reliability data | B10d = 22108; MTTFd = 23.9 years |
| Product weight | 0.15 kg |
| Standards | IEC 60947-1; IEC 60584-1 |
| Product certifications | CSA; UL; GL |
| Fire resistance | 850 °C conforming to IEC 60695-2-1; 850 °C conforming to UL |
| Shock resistance | 50 gn for 11 ms conforming to IEC 60068-2-27 |
| Vibration resistance | 5 gn (f= 10…100 Hz) conforming to IEC 60068-2-6 |
| Resistance to electrostatic discharge | 6 kV (in contact) conforming to IEC 61000-4-2 level 3; 8 kV (in air) conforming to IEC 61000-4-2 level 3 |
| Resistance to fast transients | 1 kV (on input-output) conforming to IEC 61000-4-4; 2 kV (on power supply) conforming to IEC 61000-4-4 |
| Disturbance radiated/conducted | CISPR 11; CISPR 22 group 1 - class B |
| Ambient air temperature for storage | -40…85 °C |
| Ambient air temperature for operation | 0…50 °C mounting side by side; 0…60 °C 2 cm spacing |
| Pollution degree | 2 conforming to IEC 60664-1 |
| Number of Units in Package 1 | 1 |
| Number of Units in Package 2 | 33 |
| Number of Units in Package 3 | 528 |
| Country of origin | ID |
| Warranty (in months) | 18 |
| Model | Through-feed current converter |
| Rated primary current | 15 A |
| Rated secondary current | 0.02 A |
| Accuracy class | 1 |
| Overcurrent limiting factor | FS 10 |
| Calibrated | Yes |
| With contact protection | Yes |
| Height opening | 78 mm |
| Width opening | 51 mm |
| Snap mounting | Yes |
| With copper rail | Yes |
| Number of primary inputs | 1 |
| Secondary connection | Screw connection |