| Manufacturer part number (MPN) | LTMEV40FM |
| EAN / GTIN | 3389119404938 |
| Sales unit | pcs |
| Voltage | 230 V AC |
| Range | TeSys |
| Product name | TeSys T |
| Device short name | LTME |
| Product or component type | Extension module |
| Device application | Equipment monitoring and control |
| Range compatibility | TeSys TeSys T LTMR motor controller |
| Supply | Via the controller |
| [Ui] rated insulation voltage | 690 V conforming to EN/IEC 60947-1; 690 V conforming to CSA C22.2 No 14; 690 V conforming to UL 508 |
| [Uimp] rated impulse withstand voltage | 4 kV supply, inputs and outputs conforming to EN/IEC 60947-4-1; 6 kV current or voltage measurement circuit conforming to EN/IEC 60947-4-1 |
| Logic input number | 4 |
| Input current | 3.1 mA at 100 V; 7.5 mA at 240 V |
| Current state 0 guaranteed | Logic input: 0...40 V and 2...15 mA for 25 ms |
| Current state 1 guaranteed | Logic input: 79...264 V and <= 15 mA for 25 ms |
| maximum output switching frequency | 2 Hz |
| maximum operating rate | 1800 cyc/h |
| Contacts type and composition | Without |
| Metering type | Imbalance voltage; Active power P, P1, P2, P3; Calculated active and reactive energy (+/- W.h, +/- VAR.h); Voltage U21, U32, U13, V1, V2, V3; Reactive power Q, Q1, Q2, Q3; Frequency; Power factor |
| Measurement accuracy | 1 % voltage (100...830 V); 3 % power factor; 5 % active and reactive power |
| Overvoltage category | III |
| Connection pitch | 5.08 mm |
| Connections - terminals | Control circuit: connector 1 cable(s) 0.25…2.5 mm² (24 AWG...14 AWG) flexible with cable end; Control circuit: connector 1 cable(s) 0.2…2.5 mm² (24 AWG...14 AWG) flexible without cable end; Control circuit: connector 1 cable(s) 0.25…2.5 mm² (24 AWG...14 AWG) flexible without cable end; Control circuit: connector 1 cable(s) 0.2…2.5 mm² (24 AWG...14 AWG) solid without cable end; Control circuit: connector 2 cable(s) 0.2…1 mm² (24 AWG...14 AWG) flexible with cable end; Control circuit: connector 2 cable(s) 0.2…1.5 mm² (24 AWG...14 AWG) flexible without cable end; Control circuit: connector 2 cable(s) 0.5…1.5 mm² (24 AWG...14 AWG) flexible without cable end; Control circuit: connector 2 cable(s) 0.2…1 mm² (24 AWG...14 AWG) solid without cable end |
| Tightening torque | Control circuit: 0.5…0.6 N.m flat screwdriver 3 mm |
| Pollution degree | 3 |
| Electromagnetic compatibility | Electrostatic discharge, 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2; Fast transients immunity test (other circuits), level 3, 2 kV, conforming to EN/IEC 61000-4-4; Fast transients immunity test (on supply and relay outputs), level 4, 4 kV, conforming to EN/IEC 61000-4-4; Conducted RF disturbances, 10 V, conforming to EN/IEC 61000-4-6; Control circuit: surges (serial mode), 1 kV, conforming to EN/IEC 61000-4-5; Communication: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5; Voltage inputs: surges (serial mode), 2 kV, conforming to EN/IEC 61000-4-5; Voltage inputs: surges (common mode), 4 kV, conforming to EN/IEC 61000-4-5; Control circuit: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5 |
| Width | 45 mm |
| Height | 61 mm |
| Depth | 120.7 mm |
| Product weight | 0.21 kg |
| Compatibility code | LTME |
| Standards | CSA C22.2 No 14; IACS E10; IEC 60947-4-1; UL 508; EN 60947-4-1 |
| Product certifications | LROS (Lloyds register of shipping); ATEX; NOM; EAC; RMRoS; GL; UL; DNV; BV; RINA; KERI; C-Tick; CSA; CCC; ABS |
| IP degree of protection | IP20 |
| Protective treatment | 12 x 24 hour cycles conforming to EN/IEC 60068-2-30; 48 h conforming to EN/IEC 60070-2-11; TH conforming to EN/IEC 60068 |
| Fire resistance | 650 °C conforming to EN/IEC 60695-2-12; 960 °C conforming to UL 94 |
| Ambient air temperature for operation | -20…60 °C |
| Ambient air temperature for storage | -40…80 °C |
| Operating altitude | <= 2000 m without derating |
| Mechanical robustness | Shocks half its wave acceleration: 15 Gn for 11 ms conforming to EN/IEC 60068-2-27; Vibrations mounted on symmetrical rail: 1 Gn, 5...300 Hz conforming to EN/IEC 60068-2-6; Vibrations plate mounted: 4 Gn, 5...300 Hz conforming to EN/IEC 60068-2-6 |
| Number of Units in Package 1 | 1 |
| Number of Units in Package 2 | 20 |
| Country of origin | CN |
| Warranty (in months) | 18 |
| Model | Digital module |
| Rated control supply voltage AC 50 Hz | 100–240 V |
| Rated control supply voltage AC 60 Hz | 100–240 V |
| Voltage type for actuating | AC |
| Number of digital inputs | 4 |
| Input for thermistor connection | No |
| Input for earth fault detection | No |
| Input for analogue temperature sensor | No |
| Degree of protection (IP) | IP20 |