cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Tesys T Canop 1,35-27A 230VAC (LTMR27CFM)

Schneider Electric · Electrical Components · France · se.com
Part Number
LTMR27CFM  ·  HS 8537.10
Tesys T Canop 1,35-27A 230VAC (LTMR27CFM)

Schneider Electric LTMR27CFM TeSys T CanOp 1,35-27A 230VAC.

Technical Specifications

Manufacturer part number (MPN)LTMR27CFM
EAN / GTIN3389119404716
Sales unitpcs
Package quantity10 pcs
Voltage230 V AC
Setting range1.35-27 A
RangeTeSys
Product nameTeSys T
Device short nameLTMR
Product or component typeMotor controller
Device applicationEquipment monitoring and control
Measurement current1.35…27 A
[Us] rated supply voltage100...240 V AC 50/60 Hz
Current consumption8...62.8 mA
Supply voltage limits93.5…264 V AC
Communication port protocolCANopen
Bus typeCANopen ISO 1198 interface, addressing 1...127, transmission rate 10...1000 kbit/s, SUB-D 9 with 4 twisted shielded pairs cable; CANopen ISO 1198 interface, addressing 1...127, transmission rate 10...1000 kbit/s, terminal block with 4 twisted shielded pairs cable
[Ui] rated insulation voltage690 V conforming to EN/IEC 60947-1; 690 V conforming to CSA C22.2 No 14; 690 V conforming to UL 508
[Uimp] rated impulse withstand voltage4 kV supply, inputs and outputs conforming to EN/IEC 60947-4-1; 6 kV current or voltage measurement circuit conforming to EN/IEC 60947-4-1; 0.8 kV communication circuit conforming to EN/IEC 60947-4-1
Short-circuit withstand100 kA conforming to EN/IEC 60947-4-1
Associated fuse rating4 A gG for output; 0.5 A gG for control circuit
Protection typeOverload (long time); Power factor variation; Phase unbalance; Reverse polarity protection; Locked rotor; Thermal overload protection; Earth-leakage protection; Thermal protection; Phase failure; Overload; Load fluctuation
Network and machine diagnosis typeTrip history information; Starting current and time; Fault recording; Running hours counter/operating time; Motor control command recording; Phase fault and earth fault trip counters; Waiting time after overload tripping; Remaining operating time before overload tripping; Trip context information; Event recording
Logic input number6
Input current3.1 mA at 100 V; 7.5 mA at 240 V
Current state 0 guaranteedLogic input: 0...40 V and <= 15 mA for 25 ms
Current state 1 guaranteedLogic input: 79...264 V and >= 2 mA for 25 ms
maximum output switching frequency2 Hz
Load current5 A at 250 V AC for logic output; 5 A at 30 V DC for logic output
Permissible power480 VA (AC-15), Ie = 2 A, 500000 cycles (output); 30 W (DC-13), Ie = 1.25 A, 500000 cycles (output)
maximum operating rate1800 cyc/h
Contacts type and composition1 NO + 1 NC fault signal; 3 NO
Metering typeTemperature; Earth-fault current; Phase current I1, I2, I3 RMS; Imbalance current; Average current Iavg
Measurement accuracy5...15 % earth fault current internal measurement; 1 % voltage (100...830 V); 3 % power factor; 5 % earth fault current external measurement; +/- 30 min/year internal clock; 0,02 temperature; 1 % current; 5 % active and reactive power
Overvoltage categoryIII
Connection pitch5.08 mm
Connections - terminalsControl circuit: connector 1 cable(s) 0.25…2.5 mm² (24 AWG...14 AWG) flexible with cable end; Control circuit: connector 1 cable(s) 0.2…2.5 mm² (24 AWG...14 AWG) flexible without cable end; Control circuit: connector 1 cable(s) 0.25…2.5 mm² (24 AWG...14 AWG) flexible without cable end; Control circuit: connector 1 cable(s) 0.2…2.5 mm² (24 AWG...14 AWG) solid without cable end; Control circuit: connector 2 cable(s) 0.2…1 mm² (24 AWG...14 AWG) flexible with cable end; Control circuit: connector 2 cable(s) 0.2…1.5 mm² (24 AWG...14 AWG) flexible without cable end; Control circuit: connector 2 cable(s) 0.5…1.5 mm² (24 AWG...14 AWG) flexible without cable end; Control circuit: connector 2 cable(s) 0.2…1 mm² (24 AWG...14 AWG) solid without cable end
Tightening torqueControl circuit: 0.5…0.6 N.m flat screwdriver 3 mm
Pollution degree3
Electromagnetic compatibilityElectrostatic discharge, 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2; Radiated RF fields, 3, 10 V/m, conforming to EN/IEC 61000-4-3; Fast transients immunity test (other circuits), level 3, 2 kV, conforming to EN/IEC 61000-4-4; Fast transients immunity test (on supply and relay outputs), level 4, 4 kV, conforming to EN/IEC 61000-4-4; Voltage dips and interruptions immunity test, 70 %, 500 ms, conforming to EN/IEC 61000-4-11; Conducted RF disturbances, 10 V, conforming to EN/IEC 61000-4-6; Temperature sensor: surges (serial mode), 0.5 kV, conforming to EN/IEC 61000-4-5; Temperature sensor: surges (common mode), 1 kV, conforming to EN/IEC 61000-4-5; Control circuit: surges (serial mode), 1 kV, conforming to EN/IEC 61000-4-5; Communication: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5; Relay outputs and supply: surges (serial mode), 2 kV, conforming to EN/IEC 61000-4-5; Relay outputs and supply: surges (common mode), 4 kV, conforming to EN/IEC 61000-4-5; Control circuit: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5
Width91 mm
Height61 mm
Depth122.5 mm
Product weight0.53 kg
Web servicesWeb server
Compatibility codeLTMR
StandardsIACS E10; CSA C22.2 No 14; EN 60947-4-1; IEC 60947-4-1; UL 508
Product certificationsNOM; LROS (Lloyds register of shipping); DNV; C-Tick; ABS; ATEX; CSA; EAC; BV; GL; CCC; RMRoS; UL; KERI; RINA
Protective treatment12 x 24 hour cycles conforming to EN/IEC 60068-2-30; 48 h conforming to EN/IEC 60070-2-11; TH conforming to EN/IEC 60068
Fire resistance650 °C conforming to EN/IEC 60695-2-12; 960 °C conforming to UL 94
Ambient air temperature for operation-20…60 °C
Ambient air temperature for storage-40…80 °C
Operating altitude<= 2000 m without derating
Mechanical robustnessVibrations mounted on symmetrical rail: 1 Gn, 5...300 Hz conforming to EN/IEC 60068-2-6; Vibrations plate mounted: 4 Gn, 5...300 Hz conforming to EN/IEC 60068-2-6; Shocks half its wave acceleration: 15 Gn for 11 ms conforming to EN/IEC 60068-2-27
IP degree of protectionIP20
Country of originCN
Warranty (in months)18
Supply voltage AC 50 Hz93.5–264 V
Supply voltage AC 60 Hz93.5–264 V
Voltage type (supply voltage)AC
Rated operation current Ie1.35–27 A
Rated voltage Ue at AC 50 Hz93.5–264 V
Rated voltage Ue at AC 60 Hz93.5–264 V
Rated operating frequency50–60 Hz
Current detection moduleYes
Voltage detection moduleNo
Type of connection systemScrew connection
Rated control supply voltage AC 50 Hz100–240 V
Rated control supply voltage AC 60 Hz100–240 V
Voltage type for actuatingAC
Number of outputs, with contact5
Number of electronic outputs3
Input for thermistor connectionYes
Input for earth fault detectionYes
Input for analogue temperature sensorYes
Type of interfaceCANOpen
Degree of protection (IP)IP20
Number of digital inputs6

Properties

MOQ1

Cross-References

Attached Documents