cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Schneider Electric Motor Management, TeSys T, motor controller, Modbus, 6 inputs, 3 outputs, 5 to 100A, 100 to 240 VAC LTMR100MFM

Schneider Electric · Electric Motors · Electric Motors · France · se.com
Part Number
LTMR100MFM  ·  HS 8537.10
Schneider Electric Motor Management, TeSys T, motor controller, Modbus, 6 inputs, 3 outputs, 5 to 100A, 100 to 240 VAC LTMR100MFM

Schneider Electric motor controller LTMR TeSys T - 100.240 V AC 100 A for Modbus.

Technical Specifications

Manufacturer part number (MPN)LTMR100MFM
EAN / GTIN3389119404679
Sales unitpcs
Package quantity10 pcs
Voltage230 V AC
Setting range5-100 A
RangeTeSys
Product nameTeSys T
Device short nameLTMR
Product or component typeMotor controller
Device applicationEquipment monitoring and control
Measurement current5…100 A
[Us] rated supply voltage100...240 V AC 50/60 Hz
Current consumption8...62.8 mA
Supply voltage limits93.5…264 V AC
Communication port protocolModbus
Bus typeModbus 2-wire RS 485 interface, addressing 1...247, transmission rate 1.2...19.2 kbit/s, RJ45 with 2 shielded twisted pairs; Modbus 2-wire RS 485 interface, addressing 1...247, transmission rate 1.2...19.2 kbit/s, terminal block with 2 shielded twisted pairs
[Ui] rated insulation voltage690 V conforming to EN/IEC 60947-1; 690 V conforming to CSA C22.2 No 14; 690 V conforming to UL 508
[Uimp] rated impulse withstand voltage4 kV supply, inputs and outputs conforming to EN/IEC 60947-4-1; 6 kV current or voltage measurement circuit conforming to EN/IEC 60947-4-1; 0.8 kV communication circuit conforming to EN/IEC 60947-4-1
Short-circuit withstand100 kA conforming to EN/IEC 60947-4-1
Associated fuse rating4 A gG for output; 0.5 A gG for control circuit
Protection typeLoad fluctuation; Earth-leakage protection; Overload (long time); Overload; Locked rotor; Thermal protection; Thermal overload protection; Power factor variation; Reverse polarity protection; Phase failure; Phase unbalance
Network and machine diagnosis typeMotor control command recording; Starting current and time; Trip history information; Phase fault and earth fault trip counters; Running hours counter/operating time; Remaining operating time before overload tripping; Fault recording; Trip context information; Event recording; Waiting time after overload tripping
Logic input number6
Input current3.1 mA at 100 V; 7.5 mA at 240 V
Current state 0 guaranteedLogic input: 0...40 V and <= 15 mA for 25 ms
Current state 1 guaranteedLogic input: 79...264 V and >= 2 mA for 25 ms
maximum output switching frequency2 Hz
Load current5 A at 250 V AC for logic output; 5 A at 30 V DC for logic output
Permissible power480 VA (AC-15), Ie = 2 A, 500000 cycles (output); 30 W (DC-13), Ie = 1.25 A, 500000 cycles (output)
maximum operating rate1800 cyc/h
Contacts type and composition1 NO + 1 NC fault signal; 3 NO
Metering typeTemperature; Earth-fault current; Average current Iavg; Imbalance current; Phase current I1, I2, I3 RMS
Measurement accuracy5...15 % earth fault current internal measurement; 1 % voltage (100...830 V); 3 % power factor; 5 % earth fault current external measurement; +/- 30 min/year internal clock; 0,02 temperature; 5 % active and reactive power; 0,02 current
Overvoltage categoryIII
Connection pitch5.08 mm
Connections - terminalsControl circuit: connector 1 cable(s) 0.25…2.5 mm² (24 AWG...14 AWG) flexible with cable end; Control circuit: connector 1 cable(s) 0.2…2.5 mm² (24 AWG...14 AWG) flexible without cable end; Control circuit: connector 1 cable(s) 0.25…2.5 mm² (24 AWG...14 AWG) flexible without cable end; Control circuit: connector 1 cable(s) 0.2…2.5 mm² (24 AWG...14 AWG) solid without cable end; Control circuit: connector 2 cable(s) 0.2…1 mm² (24 AWG...14 AWG) flexible with cable end; Control circuit: connector 2 cable(s) 0.2…1.5 mm² (24 AWG...14 AWG) flexible without cable end; Control circuit: connector 2 cable(s) 0.5…1.5 mm² (24 AWG...14 AWG) flexible without cable end; Control circuit: connector 2 cable(s) 0.2…1 mm² (24 AWG...14 AWG) solid without cable end
Tightening torqueControl circuit: 0.5…0.6 N.m flat screwdriver 3 mm
Pollution degree3
Electromagnetic compatibilityElectrostatic discharge, 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2; Radiated RF fields, 3, 10 V/m, conforming to EN/IEC 61000-4-3; Fast transients immunity test (other circuits), level 3, 2 kV, conforming to EN/IEC 61000-4-4; Fast transients immunity test (on supply and relay outputs), level 4, 4 kV, conforming to EN/IEC 61000-4-4; Voltage dips and interruptions immunity test, 70 %, 500 ms, conforming to EN/IEC 61000-4-11; Conducted RF disturbances, 10 V, conforming to EN/IEC 61000-4-6; Temperature sensor: surges (serial mode), 0.5 kV, conforming to EN/IEC 61000-4-5; Temperature sensor: surges (common mode), 1 kV, conforming to EN/IEC 61000-4-5; Control circuit: surges (serial mode), 1 kV, conforming to EN/IEC 61000-4-5; Communication: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5; Relay outputs and supply: surges (serial mode), 2 kV, conforming to EN/IEC 61000-4-5; Relay outputs and supply: surges (common mode), 4 kV, conforming to EN/IEC 61000-4-5; Control circuit: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5
Width91 mm
Height61 mm
Depth122.5 mm
Product weight0.53 kg
Web servicesWeb server
Compatibility codeLTMR
StandardsIACS E10; IEC 60947-4-1; UL 508; EN 60947-4-1; CSA C22.2 No 14
Product certificationsLROS (Lloyds register of shipping); UL; ABS; ATEX; EAC; CCC; BV; RINA; DNV; C-Tick; RMRoS; CSA; GL; NOM; KERI
Protective treatment12 x 24 hour cycles conforming to EN/IEC 60068-2-30; 48 h conforming to EN/IEC 60070-2-11; TH conforming to EN/IEC 60068
Fire resistance650 °C conforming to EN/IEC 60695-2-12; 960 °C conforming to UL 94
Ambient air temperature for operation-20…60 °C
Ambient air temperature for storage-40…80 °C
Operating altitude<= 2000 m without derating
Mechanical robustnessVibrations mounted on symmetrical rail: 1 Gn, 5...300 Hz conforming to EN/IEC 60068-2-6; Vibrations plate mounted: 4 Gn, 5...300 Hz conforming to EN/IEC 60068-2-6; Shocks half its wave acceleration: 15 Gn for 11 ms conforming to EN/IEC 60068-2-27
IP degree of protectionIP20
Country of originCN
Warranty (in months)18
Supply voltage AC 50 Hz93.5–264 V
Supply voltage AC 60 Hz93.5–264 V
Voltage type (supply voltage)AC
Rated operation current Ie5–100 A
Rated voltage Ue at AC 50 Hz93.5–264 V
Rated voltage Ue at AC 60 Hz93.5–264 V
Rated operating frequency50–60 Hz
Current detection moduleYes
Voltage detection moduleNo
Type of connection systemScrew connection
Voltage type for actuatingAC
Number of outputs, with contact5
Number of electronic outputs3
Input for thermistor connectionYes
Input for earth fault detectionYes
Input for analogue temperature sensorYes
Type of interfaceModbus
Degree of protection (IP)IP20
Number of digital inputs6

Properties

MOQ1

Cross-References

Attached Documents