| Manufacturer part number (MPN) | ATV12PU15M3 |
| EAN / GTIN | 3606480071232 |
| Sales unit | pcs |
| Package quantity | 30 pcs |
| Power | 1.5 kW |
| Range of product | Altivar 12 |
| Product or component type | Variable speed drive |
| Product specific application | Simple machine |
| mounting mode | Cabinet mount |
| Communication port protocol | Modbus |
| Supply frequency | 50/60 Hz +/- 5 % |
| [Us] rated supply voltage | 200...240 V - 15...10 % |
| nominal output current | 7.5 A |
| Motor power kW | 1.5 kW |
| Motor power hp | 2 hp |
| EMC filter | Without EMC filter |
| IP degree of protection | IP20 |
| Discrete input number | 4 |
| Discrete output number | 2 |
| Analogue input number | 1 |
| Analogue output number | 1 |
| Relay output number | 1 |
| Physical interface | 2-wire RS 485 |
| Connector type | 1 RJ45 |
| Continuous output current | 7.5 A at 4 kHz |
| Method of access | Server Modbus serial |
| Speed drive output frequency | 0.5…400 Hz |
| Speed range | 1…20 |
| Sampling duration | 20 ms, tolerance +/- 1 ms for logic input; 10 ms for analogue input |
| Linearity error | +/- 0.3 % of maximum value for analogue input |
| Frequency resolution | Analog input: converter A/D, 10 bits; Display unit: 0.1 Hz |
| Time constant | 20 ms +/- 1 ms for reference change |
| Transmission rate | 9.6 kbit/s; 19.2 kbit/s; 38.4 kbit/s |
| Transmission frame | RTU |
| Number of addresses | 1…247 |
| Data format | 8 bits, configurable odd, even or no parity |
| Communication service | Read holding registers (03) 29 words; Write single register (06) 29 words; Write multiple registers (16) 27 words; Read/write multiple registers (23) 4/4 words; Read device identification (43) |
| Type of polarization | No impedance |
| 4 quadrant operation possible | False |
| Asynchronous motor control profile | Voltage/frequency ratio (V/f); Sensorless flux vector control; Quadratic voltage/frequency ratio |
| Maximum output frequency | 4 kHz |
| Transient overtorque | 150…170 % of nominal motor torque depending on drive rating and type of motor |
| Acceleration and deceleration ramps | U; S; Linear from 0 to 999.9 s |
| Motor slip compensation | Adjustable; Preset in factory |
| Switching frequency | 2...16 kHz adjustable; 4...16 kHz with derating factor |
| Nominal switching frequency | 4 kHz |
| Braking to standstill | By DC injection |
| Brake chopper integrated | False |
| Line current | 11.1 A at 100 V (heavy duty); 9.3 A at 120 V (heavy duty) |
| Maximum input current | 9.3 A |
| Maximum output voltage | 240 V |
| Apparent power | 3.9 kVA at 240 V (heavy duty) |
| Maximum transient current | 11.2 A during 60 s (heavy duty); 12.4 A during 2 s (heavy duty) |
| Network frequency | 50...60 Hz |
| Relative symmetric network frequency tolerance | 5 % |
| Prospective line Isc | 5 kA |
| Base load current at high overload | 7.5 A |
| Power dissipation in W | Natural: 73.0 W |
| With safety function Safely Limited Speed (SLS) | False |
| With safety function Safe brake management (SBC/SBT) | False |
| With safety function Safe Operating Stop (SOS) | False |
| With safety function Safe Position (SP) | False |
| With safety function Safe programmable logic | False |
| With safety function Safe Speed Monitor (SSM) | False |
| With safety function Safe Stop 1 (SS1) | False |
| With sft fct Safe Stop 2 (SS2) | False |
| With safety function Safe torque off (STO) | False |
| With safety function Safely Limited Position (SLP) | False |
| With safety function Safe Direction (SDI) | False |
| Protection type | Line supply overvoltage; Line supply undervoltage; Overcurrent between output phases and earth; Overheating protection; Short-circuit between motor phases; Against input phase loss in three-phase; Thermal motor protection via the drive by continuous calculation of I²t |
| Tightening torque | 1.2 N.m |
| Insulation | Electrical between power and control |
| Quantity per set | Set of 1 |
| Width | 105 mm |
| Height | 143 mm |
| Depth | 98.2 mm |
| Product weight | 1 kg |
| Operating altitude | 1000...3000 m with current derating 1 % per 100 m |
| Operating position | Vertical +/- 10 degree |
| Product certifications | NOM; CSA; C-Tick; UL; GOST; RCM; KC |
| Marking | CE |
| Standards | UL 508C; UL 618000-5-1; IEC 61800-5-1; IEC 61800-3 |
| Assembly style | On base plate |
| Electromagnetic compatibility | Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4; Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2; Immunity to conducted disturbances level 3 conforming to IEC 61000-4-6; Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3; Surge immunity test level 3 conforming to IEC 61000-4-5; Voltage dips and interruptions immunity test conforming to IEC 61000-4-11 |
| Environmental class (during operation) | Class 3C3 according to IEC 60721-3-3; Class 3S2 according to IEC 60721-3-3 |
| Maximum acceleration under shock impact (during operation) | 150 m/s² at 11 ms |
| Maximum deflection under vibratory load (during operation) | 1.5 mm at 2...13 Hz |
| Overvoltage category | Class III |
| Regulation loop | Adjustable PID regulator |
| Electromagnetic emission | Radiated emissions environment 1 category C2 conforming to IEC 61800-3 2...16 kHz shielded motor cable; Conducted emissions with additional EMC filter environment 1 category C1 conforming to IEC 61800-3 4...12 kHz shielded motor cable <5 m; Conducted emissions with additional EMC filter environment 1 category C2 conforming to IEC 61800-3 4...12 kHz shielded motor cable <20 m; Conducted emissions with additional EMC filter environment 2 category C3 conforming to IEC 61800-3 4...12 kHz shielded motor cable <20 m |
| Vibration resistance | 1 gn (f = 13…200 Hz) conforming to IEC 60068-2-6; 1.5 mm peak to peak (f = 3…13 Hz) - drive unmounted on symmetrical DIN rail - conforming to IEC 60068-2-6 |
| Shock resistance | 15 gn conforming to IEC 60068-2-27 for 11 ms |
| Relative humidity | 5…95 % without condensation conforming to IEC 60068-2-3; 5…95 % without dripping water conforming to IEC 60068-2-3 |
| Noise level | 0 dB |
| Pollution degree | 2 |
| Ambient air transport temperature | -25…70 °C |
| Ambient air temperature for operation | -10…40 °C without derating; 40…60 °C with current derating 2.2 % per °C |
| Ambient air temperature for storage | -25…70 °C |
| Number of Units in Package 1 | 1 |
| Number of Units in Package 2 | 30 |
| Country of origin | ID |
| Warranty (in months) | 18 |
| With control element | Yes |
| Number of digital inputs | 4 |
| Number of digital outputs | 1 |
| Number of analogue inputs | 1 |
| Number of analogue outputs | 1 |
| Supporting protocol for LON | No |
| Number of HW-interfaces RS-485 | 1 |
| Number of HW-interfaces other | 8 |
| With optical interface | No |
| Supporting protocol for TCP/IP | No |
| Supporting protocol for ASI | No |
| Supporting protocol for PROFIBUS | No |
| Supporting protocol for CAN | No |
| Supporting protocol for INTERBUS | No |
| Supporting protocol for KNX | No |
| Supporting protocol for Modbus | Yes |
| Supporting protocol for Data-Highway | No |
| Supporting protocol for DeviceNet | No |
| Supporting protocol for SUCONET | No |
| Supporting protocol for other bus systems | No |
| Degree of protection (IP) | IP20 |
| With PC connection | Yes |
| Supporting protocol for SERCOS | No |
| Supporting protocol for INTERBUS-Safety | No |
| Mains voltage | 200–240 V |
| Mains frequency | 50/60 Hz |
| Type of converter | U converter |
| Number of phases output | 3 |
| Number of phases input | 3 |
| Integrated breaking resistance | No |
| Application in industrial area permitted | Yes |
| Application in domestic- and commercial area permitted | Yes |
| Max. output frequency | 400 Hz |
| Max. output at linear load at rated output voltage | 1.5 kW |
| Max. output at quadratic load at rated output voltage | 1.5 kW |
| Relative symmetric net voltage tolerance | 10 % |
| Relative symmetric net frequency tolerance | 5 % |
| Supporting protocol for AS-Interface Safety at Work | No |
| Supporting protocol for DeviceNet Safety | No |
| Supporting protocol for EtherNet/IP | No |
| Supporting protocol for Foundation Fieldbus | No |
| Supporting protocol for PROFINET CBA | No |
| Supporting protocol for PROFINET IO | No |
| Supporting protocol for PROFIsafe | No |
| Supporting protocol for SafetyBUS p | No |
| Max. output voltage | 230 V |
| Nominal output current I2N | 7.5 A |
| Supporting protocol for BACnet | No |