cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Reversing Switch V. 32A 24V DC (LU6MB0BL)

Schneider Electric · Electrical Components · Contactors · France · se.com
Part Number
LU6MB0BL  ·  HS 8536.41
Reversing Switch V. 32A 24V DC (LU6MB0BL)

Schneider Electric LU6MB0BL Reversing contactor module 32A 24VDC.

Technical Specifications

Manufacturer part number (MPN)LU6MB0BL
EAN / GTIN3389110106183
Sales unitpcs
Package quantity10 pcs
Voltage24 V
Rated current32 A
RangeTeSys
Device short nameLU6MB
Product or component typeReverser block
Device mountingSeparate mounting
Device applicationMotor control
[Ie] rated operational current38 A
[Uc] control circuit voltage24 V DC
Current consumption120 mA at 24 V DC I maximum while closing; 120 mA at 24 V DC I rms sealed
[Ue] rated operational voltage690 V AC power circuit
Network frequency40...60 Hz
Inrush restraint duration25 ms AC; 15 ms DC
Operating time150 ms with change of direction; 75 ms without change of direction
StandardsEN 60947-6-2; IEC 60947-6-2; UL 60947-4-1, with phase barrier; CSA C22.2 No 60947-4-1, with phase barrier
Product certificationsCE; UL; CSA; CCC; EAC; ASEFA; ATEX; Marine
[Ui] rated insulation voltage690 V conforming to IEC 60947-6-2; 600 V conforming to UL 60947-4-1; 600 V conforming to CSA C22.2 No 60947-4-1
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947-6-2
Fixing modeClipped (DIN rail); Screw-fixed (plate)
Connections - terminalsControl circuit: screw clamp terminals 1 cable(s) 0.34…1.5 mm² (external diameter: 3 mm) flexible with cable end; Control circuit: screw clamp terminals 1 cable(s) 0.75…1.5 mm² (external diameter: 3 mm) flexible without cable end; Control circuit: screw clamp terminals 1 cable(s) 0.75…1.5 mm² (external diameter: 3 mm) rigid; Control circuit: screw clamp terminals 2 cable(s) 0.34…1.5 mm² (external diameter: 3 mm) flexible with cable end; Control circuit: screw clamp terminals 2 cable(s) 0.75…1.5 mm² (external diameter: 3 mm) flexible without cable end; Control circuit: screw clamp terminals 2 cable(s) 0.75…1.5 mm² (external diameter: 3 mm) rigid; Power circuit: screw clamp terminals 1 cable(s) 1…10 mm² (external diameter: 4 mm) rigid; Power circuit: screw clamp terminals 1 cable(s) 1…6 mm² (external diameter: 4 mm) flexible with cable end; Power circuit: screw clamp terminals 1 cable(s) 2.5…10 mm² (external diameter: 4 mm) flexible without cable end; Power circuit: screw clamp terminals 2 cable(s) 1…6 mm² (external diameter: 4 mm) flexible with cable end; Power circuit: screw clamp terminals 2 cable(s) 1…6 mm² (external diameter: 4 mm) rigid; Power circuit: screw clamp terminals 2 cable(s) 1.5…6 mm² (external diameter: 4 mm) flexible without cable end
Tightening torqueControl circuit: 0.8…1.2 N.m flat screwdriver 5 mm; Control circuit: 0.8…1.2 N.m Philips No 2 screwdriver 5 mm; Power circuit: 1.9…2.5 N.m flat screwdriver 6 mm; Power circuit: 1.9…2.5 N.m Philips No 2 screwdriver 6 mm; Power circuit: 1.9…2.5 N.m pozidriv No 2 screwdriver 6 mm
Width45 mm
Height115 mm
Depth113 mm
Product weight0.425 kg
Compatibility codeLU6MB
IP degree of protectionIP20 conforming to IEC 60947-1 (front panel and wired terminals); IP20 conforming to IEC 60947-1 (other faces); IP40 conforming to IEC 60947-1 (front panel outside connection zone)
Protective treatmentTH conforming to IEC 60068
Ambient air temperature for operation-25…60 °C with LUCM; -25…70 °C with LUCA, LUCB, LUCC, LUCD
Ambient air temperature for storage-40…85 °C
Fire resistance960 °C parts supporting live components conforming to IEC 60695-2-12; 650 °C conforming to IEC 60695-2-12
Operating altitude2000 m
Shock resistance10 gn power poles open conforming to IEC 60068-2-27; 15 gn power poles closed conforming to IEC 60068-2-27
Vibration resistance2 gn (f= 5…300 Hz) power poles open conforming to IEC 60068-2-27; 4 gn (f= 5…300 Hz) power poles closed conforming to IEC 60068-2-27
Resistance to electrostatic discharge8 kV level 3, in open air conforming to IEC 61000-4-2; 8 kV level 4, on contact conforming to IEC 61000-4-2
Resistance to radiated fields10 V/m level 3 conforming to IEC 61000-4-3
Resistance to fast transients2 kV class 3 serial link conforming to IEC 61000-4-4; 4 kV class 4 all circuits except for serial link conforming to IEC 61000-4-4
Immunity to radioelectric fields10 V conforming to IEC 61000-4-6
Country of originFR
Warranty (in months)18
FunctionReversing contactor
Rated operation power at AC-3, 400 V18.5 kW
Rated operation current Ie at AC-3, 400 V38 A
Suitable for rail mountingYes
Rated control supply voltage AC 50 Hz24 V
Rated control supply voltage AC 60 Hz24 V
Rated control supply voltage DC24 V
Voltage type (operating voltage)DC
Degree of protection (IP)IP20
Type of electrical connection of main circuitScrew connection
Operating voltage AC 50 Hz690 V
Operating voltage AC 60 Hz690 V
Voltage type for actuatingDC
Rated operation power NEMA14.9 kW

Properties

MOQ1

Cross-References