Schneider Electric Advanced control unit, TeSys U, 0.15-0.6A, 1P motors, protection & diagnostic, class 10, coil 24V DC LUCCX6BL

Schneider Electric · Drives & Controllers · Motor Starters · France · se.com
Part Number
LUCCX6BL  ·  HS 8536.30
Schneider Electric Advanced control unit, TeSys U, 0.15-0.6A, 1P motors, protection & diagnostic, class 10, coil 24V DC LUCCX6BL

Schneider Electric LUCCX6BL Protection U ADV 0,15-0,6A 24VDC.

Technical Specifications

Manufacturer part number (MPN)LUCCX6BL
EAN / GTIN3389110364460
Sales unitpcs
Package quantity23 pcs
Voltage24 V DC
Setting range0.15-0.6 A
RangeTeSys
Range of productTeSys Ultra
Product nameTeSys Ultra
Device short nameLUCC
Product or component typeAdvanced control unit
Device applicationMotor control; Motor protection
Product specific applicationBasic protection and advanced functions, communication
main function availableProtection against phase failure and phase imbalance; Protection against overload and short-circuit; Earth fault protection; Manual reset
Product compatibilityPower base LUB12; Power base LUB32; Power base LUB38; Power base LUB120; Power base LUB320; Power base LUB380; Reversing contactor breaker LU2B12BL; Reversing contactor breaker LU2B32BL; Reversing contactor breaker LU2B38BL
[Ue] rated operational voltage690 V AC
Network frequency40...60 Hz
Load typeSingle-phase motor
Utilisation categoryAC-43; AC-41; AC-44
rated motor current adjustment range0.15…0.6 A
Thermal overload classClass 10 - frequency limit: 40…60 Hz - temperature compensation: -25…55 °C conforming to IEC 60947-6-2; Class 10 - frequency limit: 40…60 Hz - temperature compensation: -25…55 °C conforming to UL 508
Tripping threshold14.2 x Ir +/- 20 %
[Uc] control circuit voltage24 V DC
Control circuit voltage limits20...27 V for DC circuit 24 V in operation; 14.5 V for DC circuit 24 V drop-out
Typical current consumption130 mA at 24 V DC I maximum while closing with LUB12; 220 mA at 24 V DC I maximum while closing with LUB32; 220 mA at 24 V DC I maximum while closing with LUB38; 60 mA at 24 V DC I rms sealed with LUB12; 80 mA at 24 V DC I rms sealed with LUB32; 80 mA at 24 V DC I rms sealed with LUB38
Heat dissipation2 W for control circuit with LUB12; 3 W for control circuit with LUB32; 3 W for control circuit with LUB38
Operating time35 ms opening with LUB12 for control circuit; 35 ms opening with LUB32 for control circuit; 35 ms opening with LUB38 for control circuit; 70 ms closing with LUB12 for control circuit; 70 ms closing with LUB32 for control circuit; 70 ms closing with LUB38 for control circuit
ResetManual reset
StandardsEN 60947-6-2; IEC 60947-6-2; UL 60947-4-1, with phase barrier; CSA C22.2 No 60947-4-1, with phase barrier
Product certificationsCE; UL; CSA; CCC; EAC; ASEFA; ATEX; Marine
[Ui] rated insulation voltage690 V conforming to IEC 60947-6-2; 600 V conforming to UL 60947-4-1; 600 V conforming to CSA C22.2 No 60947-4-1
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947-6-2
Safe separation of circuit400 V SELV between the control and auxiliary circuits conforming to IEC 60947-1; 400 V SELV between the control or auxiliary circuit and the main circuit conforming to IEC 60947-1
Fixing modePlug-in (front face)
Width45 mm
Height66 mm
Depth60 mm
Compatibility codeLUCC
IP degree of protectionIP20 front panel and wired terminals conforming to IEC 60947-1; IP20 other faces conforming to IEC 60947-1; IP40 front panel outside connection zone conforming to IEC 60947-1
Protective treatmentTH conforming to IEC 60068
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-40…85 °C
Operating altitude2000 m
Fire resistance960 °C parts supporting live components conforming to IEC 60695-2-12; 650 °C conforming to IEC 60695-2-12
Shock resistance10 gn power poles open conforming to IEC 60068-2-27; 15 gn power poles closed conforming to IEC 60068-2-27
Vibration resistance2 gn, 5…300 Hz, power poles open conforming to IEC 60068-2-6; 4 gn, 5…300 Hz, power poles closed conforming to IEC 60068-2-6
Resistance to electrostatic discharge8 kV level 3 in open air conforming to IEC 61000-4-2; 8 kV level 4 on contact conforming to IEC 61000-4-2
Resistance to radiated fields10 V/m 3 conforming to IEC 61000-4-3
Resistance to fast transients2 kV class 3 serial link conforming to IEC 61000-4-4; 4 kV class 4 all circuits except for serial link conforming to IEC 61000-4-4
Immunity to radioelectric fields10 V conforming to IEC 61000-4-6
Immunity to microbreaks3 ms
Immunity to voltage dips70 % / 500 ms conforming to IEC 61000-4-11
Country of originFR
Warranty (in months)18
With transformerNo
Rated operation power at AC-3, 400 V0.09 kW
Suitable for emergency stopNo
Rated operation current Ie0.15 A
Overload release current setting0.15–0.6 A
Supporting protocol for LONNo
Supporting protocol for TCP/IPNo
Supporting protocol for ASINo
Supporting protocol for PROFIBUSNo
Supporting protocol for CANNo
Supporting protocol for INTERBUSNo
Supporting protocol for ModbusNo
Supporting protocol for Data-HighwayNo
Supporting protocol for DeviceNetNo
Supporting protocol for SUCONETNo
Supporting protocol for other bus systemsNo
External reset possibleNo
Suitable for rail mountingYes
Rated control supply voltage DC24 V
Degree of protection (IP)IP40
Supporting protocol for SERCOSNo
Supporting protocol for INTERBUS-SafetyNo
Release classCLASS 10
With short-circuit releaseYes
With fuseNo
Type of electrical connection of main circuitScrew connection
Supporting protocol for AS-Interface Safety at WorkNo
Supporting protocol for DeviceNet SafetyNo
Supporting protocol for EtherNet/IPNo
Supporting protocol for Foundation FieldbusNo
Supporting protocol for PROFINET CBANo
Supporting protocol for PROFINET IONo
Supporting protocol for PROFIsafeNo
Supporting protocol for SafetyBUS pNo
Voltage type for actuatingDC
Rated operation current at AC-3, 400 V0.6 A
Ambient temperature, upper operating limit70 °C
Temperature compensated overload protectionYes
Rated conditional short-circuit current, type 2, 400 V0.6 A
Rated conditional short-circuit current, type 2, 230 V0.15 A
Rated conditional short-circuit current, type 1, 480 Y/277 V0.15 A
Rated conditional short-circuit current, type 1, 600 Y/347 V0.6 A
Coordination class according to IEC 60947-4-3Class 2