cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

IM400 ISOLASJONSOVERV. IT System (IMD-IM400)

Schneider Electric · France · se.com
Part Number
IMD-IM400  ·  HS 9030.39
IM400 ISOLASJONSOVERV. IT System (IMD-IM400)

Schneider Electric IMD-IM400 Vigilohm IM400. For IT system, and DC. IM400 has large LCD display and Modbus comm..

Technical Specifications

Manufacturer part number (MPN)IMD-IM400
EAN / GTIN3606480573347
Sales unitpcs
Package quantity8 pcs
RangeVigilohm
Device short nameIM400
Product or component typeInsulation monitoring device
Type of IMDAC/DC IMD
Earthing systemIT; HRG
ApplicationMarine and offshore; Industry; Infrastructure; Power generation; Port, airport, railway
Network sizeLarge
Electrical circuit typePower circuit; Control circuit
Network capacitanceVery capacitive
Type of network1P + N; 3P; 3P + N
Network rated voltage0…480 V - AC at 45...440 Hz (device connected to phase) ; 0…830 V - AC at 45...440 Hz (device connected to neutral) ; 0…480 V - DC
Alarm threshold settingPre-alarm: 1 kOhm...1 MOhm; Alarm: 40 Ohm...500 kOhm
Type of measurementNetwork insulation resistance, range: 10 Ohm...10 MOhm, accuracy: +/- 1 %; Earth leakage capacitance, range: 0.01...500 µF, accuracy: +/- 5 %
Configurable filtering time4 s; 40 s; 400 s
Response time0.8 s 1/5th of set filtering time; 8 s 1/5th of set filtering time; 80 s 1/5th of set filtering time
Time delay range0...120 min for signalling circuit; 0...120 min for alarm
Power quality analysisTransient capture
Input typeContact for injection inhibition Dry contact; Contact for injection inhibition Modbus
Operating modeControl; Power
Self-testManual; Auto test at start and every 5h
Overvoltage categoryIII 300 V; II 600 V
IP degree of protectionCase: IP20; Front face: IP54
MaterialThermoplastic
Type of installationIndoor
Operating altitude<= 3000 m
Relative humidity0…92 %
Ambient air temperature for operation-25…55 °C
Ambient air temperature for storage-40…70 °C
Pollution degree2
Mounting modeFlush-mounted (panel)
Mounting positionHorizontal
Connections - terminalsRemovable screw terminal block 0.2…2.5 mm²
Product weight0.645 kg
Cut-out dimensions112 x 148 mm
Height123 mm
Width159 mm
Depth90 mm
Display typeLCD display
Information displayedResistance value; Capacitance value; Evolution of resistance in graph
User languageItalian; French; German; Chinese; Portuguese; Russian; Spanish; English
Local signallingGreen indicator light: satisfactory insulation resistance; White indicator light: below prevention threshold; Red indicator light: wiring or internal fault; Yellow indicator light: insulation fault; Yellow flashing indicator light: communication
Signal contacts composition2 C/O standard or fail-safe
Signalling circuit voltage250 V - AC at 3 A; 48 V - DC at 1 A
Communication port protocolModbus RS485
Communication of dataHMI: test reports; Dry contact: test reports
Fault event logAlarm logs; Time stamping; 30 events
Product compatibilityAutomatic fault locator
[Us] rated supply voltage100...440 V AC 50/60/400 Hz tolerance: +/- 15 %; 100...440 V DC tolerance: +/- 15 %
Power consumption in VA25 VA
Power consumption in W10 W
Overcurrent protection1 A
StandardsIEC 60364-4-41; IEC 61010-1; IEC 61557-8; UL 61010-1; IEC 61326-2-4; EN/IEC 61508 level SIL2
Product certificationsDNV; RMRS; CE; ABS; EAC; CSA; cULus; UL; EU-RO MR TA; RCM
Environmental characteristicExposure to damp heat not in service conforming to IEC 60068-2-30; Exposure to damp heat in service conforming to IEC 60068-2-56; Salt mist conforming to IEC 60068-2-52; Long-term storage class 1K22 conforming to IEC 60721-3-1; Transport class 2K11 conforming to IEC 60721-3-2; Stationary use at weather protected locations class 3K24 conforming to IEC 60721-3-3
Mechanical robustnessLong-term storage class 1M11 conforming to IEC 60721-3-1; Transport class 2M4 conforming to IEC 60721-3-2; Stationary use class 3M11 conforming to IEC 60721-3-3
Number of Units in Package 11
Number of Units in Package 24
Number of Units in Package 332
Country of originIN
Warranty (in months)18
Operating voltage AC 50 Hz0–830 V
Operating voltage AC 60 Hz0–830 V
Operating voltage DC0–480 V
External power supply requiredNo
Supply voltage AC 50 Hz100–440 V
Supply voltage AC 60 Hz100–440 V
Supply voltage DC100–440 V
Rated operating frequency45–440 Hz
Voltage measuring range0–830 V
Voltage type (operating voltage)AC/DC
Type of electric connectionScrew connection
Voltage type for actuatingAC
With detachable clampsYes
FunctionFor mixed system
Line capacity500 µF
Response value impedance 11–1000 kOhm
Response value impedance 20.1–500 kOhm
Indication of insulation valueYes
Error registration possibleYes
Number of contacts as change-over contact2

Properties

MOQ1

Cross-References

Attached Documents