cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Schneider Electric iQuick PRD8R modular surge arrester - 3 poles - 350V - with remote transfer A9L16299

Schneider Electric · Switchgear & Protection · Surge Protectors · France · se.com
Part Number
A9L16299  ·  HS 8538.90
Schneider Electric iQuick PRD8R modular surge arrester - 3 poles - 350V - with remote transfer A9L16299

Schneider Electric A9L16299 Surge protection device iQuick PRD 8r 3P.

Technical Specifications

Manufacturer part number (MPN)A9L16299
EAN / GTIN3606480387111
Sales unitpcs
Package quantity12 pcs
Number of poles3P
Range of productIQuick PRD
Product nameActi9 iQuick PRD
Product or component typeSurge arrester with pluggable cartridge
Device short nameiQuick PRD8r
Device applicationDistribution
StandardsEN 61643-11:2012; IEC 61643-11:2011
Product certificationsCE
Quality labelsNF; KEMA-KEUR
Poles description3P
Remote signallingWith
Signal contacts composition1 SD (1 C/O)
Surge arrester typeElectrical distribution network
Earthing systemTN-C; IT 230
Surge arrester class typeType 2 + 3
Surge arrester technologyMOV
[Ue] rated operational voltage400 V AC (+/- 10 %) at 50/60 Hz
Nominal discharge currentCommon mode: 2 kA (L/PE); Differential mode: 2 kA (L/N)
Maximum discharge currentCommon mode: 8 kA L/PE
[Uoc] open circuit voltage10 kV type 3 common mode L/PE
[Uc] maximum continuous operating voltageCommon mode: 350 V L/PE
Maximum [Up] voltage protection levelCommon mode 1.4 kV type 3 L/PE; Common mode 1.2 kV type 2 L/PE
Disconnector device typeIntegrated circuit breaker - Icu 25 kA
Signalling circuit voltage2 A/250 V AC 50/60 Hz
Mounting modeClip-on (DIN rail)
9 mm pitches12.7
Height94 mm
Width113.6 mm
Depth75.9 mm
Product weight0.67 kg
ColourWhite (RAL 9003)
Connections - terminalsTunnel type terminal (downside) 2.5…25 mm²; Tunnel type terminal (upside) 2.5…25 mm²
Tightening torque2.5 N.m
Compatibility codeIQuick PRD8r
IK degree of protectionIK05 conforming to IEC 62262
Relative humidity5…95 %
Operating altitude2000 m
Ambient air temperature for operation-25…60 °C
Ambient air temperature for storage-40…70 °C
Number of Units in Package 11
Number of Units in Package 212
Warranty (in months)18
System configuration DCNo
System configuration ITYes
System configuration TNNo
System configuration TN-CYes
System configuration TTNo
System configuration otherNo
Number of conductors (without earthing)3
Nominal discharge surge current (8/20)2 kA
Max. discharge surge current (8/20)8 kA
Short-circuit-proofYes
Nominal voltage AC400 V
Max. continuous voltage AC350 V
Voltage protection level1.2 kV
Voltage protection level L-N1.2 kV
Voltage protection level N-PE1.2 kV
Short-circuit breaking capacity (Isccr)25 kA
Integrated short-circuit protectionYes
Integrated backup fuseNo
Leakage-current freeNo
Mounting methodDIN rail (top hat rail) 35 mm
Max. conductor cross section solid (solid, stranded)25 mm²
Max. conductor cross section flexible (fine-strand)25 mm²
With remote signalling contactYes
Signalling at the deviceOptical
Category type 2Yes
Degree of protection (IP)IP20
Country of originHungary

Properties

MOQ1

Cross-References

Attached Documents