cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Schneider Electric A9F94302 ACTI9 IC60L Miniature Circuit Breaker 3P 2 A, Curve C

Schneider Electric · Electrical Components · Miniature Circuit Breakers · France · se.com
Part Number
A9F94302  ·  HS 8536.90
Schneider Electric A9F94302 ACTI9 IC60L Miniature Circuit Breaker 3P 2 A, Curve C

Schneider Electric A9F94302 is an Acti9 iC60L miniature circuit breaker (MCB), 3P, rated 2 A with a type C tripping curve. It provides overload and short-circuit protection for final and sub-distribution circuits on 35 mm DIN rail. The type C magnetic release operates at 8 x In (±20%), suited to general-purpose mixed resistive and inductive loads. Current-limiting design with rated breaking capacity Icn 15 000 A per IEC/EN 60898-1; ultimate breaking capacity Icu per IEC/EN 60947-2 depends on rating. Rated voltage Ue 230/400 V AC, rated insulation voltage Ui 500 V, rated impulse withstand Uimp 6 kV. Multi-standard to IEC/EN 60898-1 and IEC/EN 60947-2.

Technical Specifications

Manufacturer part number (MPN)A9F94302
EAN / GTIN3606480084485
Product typeActi9 iC60L miniature circuit breaker (MCB)
Poles3P
Rated current In2 A
Tripping curvetype C (magnetic trip 8 x In (±20%))
Rated operational voltage Ue230/400 V AC, 50/60 Hz
Rated breaking capacity Icn15 000 A (IEC/EN 60898-1); current-limiting
Rated insulation voltage Ui500 V
Rated impulse withstand voltage Uimp6 kV
Endurance20 000 mechanical / 10 000 electrical operations
Degree of protectionIP20 (terminals); IP40 in modular enclosure
Operating temperature-25 °C to +70 °C
Mounting35 mm DIN rail (clip-on)
Conforms toIEC/EN 60898-1, IEC/EN 60947-2
HS code8536.90
Sales unitpcs
Package quantity4 pcs
RangeActi9
Product nameActi9 iC60
Product or component typeMiniature circuit-breaker
Device short nameiC60L
Device applicationDistribution
Poles description3P
Number of protected poles3
[In] rated current2 A
Network typeDC; AC
Trip unit technologyThermal-magnetic
Curve codeC
Utilisation categoryCategory A conforming to EN/IEC 60947-2
Suitability for isolationYes conforming to EN/IEC 60947-2; Yes conforming to EN/IEC 60898-1
StandardsEN/IEC 60947-2; EN/IEC 60898-1
Network frequency50/60 Hz
[Ue] rated operational voltage12...133 V AC 50/60 Hz; 220...240 V AC 50/60 Hz; 380...415 V AC 50/60 Hz; 440 V AC 50/60 Hz; <= 180 V DC
Magnetic tripping limit8 x In +/- 20 %
Breaking capacity100 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2; 100 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2; 100 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2; 70 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2; 20 kA Icu at <= 180 V DC conforming to EN/IEC 60947-2; 15000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
[Ics] rated service breaking capacity100 kA 100 % x Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2; 100 kA 100 % x Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2; 100 kA 100 % x Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2; 70 kA 100 % x Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2; 20 kA 100 % x Icu at <= 180 V DC conforming to EN/IEC 60947-2
Limitation class3 conforming to EN/IEC 60898-1
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to EN/IEC 60947-2
Contact position indicatorYes
Control typeToggle
Local signallingTrip indicator
mounting modeClip-on; Removable comb busbar installed
Mounting support35 mm DIN rail
Comb busbar and distribution block compatibilityTop or bottom: YES
Connection pitch18 mm between phases
9 mm pitches6
Height85 mm
Width54 mm
Depth78.5 mm
Product weight0.375 kg
ColourWhite
Mechanical durability20000 cycles
Electrical durability10000 cycles
Connections - terminalsSingle terminal (top or bottom) , for 1 cable(s) , 1…25 mm², rigid, copper; Single terminal (top or bottom) , for 1 cable(s) , 1…16 mm², flexible, copper; Single terminal (top or bottom) , for 1 cable(s) , 1…16 mm², flexible with ferrule, copper; Single terminal (top or bottom) , for 1.0 cable(s) , flexible, copper or aluminium, with ring terminal and accessory
Wire stripping length14 mm for top or bottom connection
Tightening torque2 N.m top or bottom
Earth-leakage protectionSeparate block
IP degree of protectionIP20 conforming to IEC 60529; IP40 in modular enclosure (Insulation class II) conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Overvoltage categoryIV
Tropicalisation2 conforming to IEC 60068-1
Relative humidity95 % at 55 °C
Operating altitude0...2000 m
Ambient air temperature for operation-35…70 °C
Ambient air temperature for storage-40…85 °C
Warranty (in months)18

Properties

Primary standardIEC/EN 60898-1
MOQ1

Standards

Cross-References

Attached Documents