cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Schneider Electric A9F07102 ACTI9 IC60H Miniature Circuit Breaker 1P 2 A, Curve C

Schneider Electric · Electrical Components · Miniature Circuit Breakers · France · se.com
Part Number
A9F07102  ·  HS 8536.90
Schneider Electric A9F07102 ACTI9 IC60H Miniature Circuit Breaker 1P 2 A, Curve C

Schneider Electric A9F07102 is an Acti9 iC60H miniature circuit breaker (MCB), 1P, rated 2 A with a type C tripping curve. It provides overload and short-circuit protection for final and sub-distribution circuits on 35 mm DIN rail. The type C magnetic release operates at 8 x In (±20%), suited to general-purpose mixed resistive and inductive loads. Rated breaking capacity Icn 10 000 A per IEC/EN 60898-1 and Icu 15 kA per IEC/EN 60947-2 at 400 V. Rated voltage Ue 230/400 V AC, rated insulation voltage Ui 500 V, rated impulse withstand Uimp 6 kV. Multi-standard to IEC/EN 60898-1 and IEC/EN 60947-2.

Technical Specifications

Manufacturer part number (MPN)A9F07102
EAN / GTIN3606480438295
Product typeActi9 iC60H miniature circuit breaker (MCB)
Poles1P
Rated current In2 A
Tripping curvetype C (magnetic trip 8 x In (±20%))
Rated operational voltage Ue230/400 V AC, 50/60 Hz
Rated breaking capacity Icn10 000 A (IEC/EN 60898-1); Icu 15 kA (IEC/EN 60947-2, 400 V)
Rated insulation voltage Ui500 V
Rated impulse withstand voltage Uimp6 kV
Endurance20 000 mechanical / 10 000 electrical operations
Degree of protectionIP20 (terminals); IP40 in modular enclosure
Operating temperature-25 °C to +70 °C
Mounting35 mm DIN rail (clip-on)
Conforms toIEC/EN 60898-1, IEC/EN 60947-2
HS code8536.90
Sales unitpcs
Package quantity12 pcs
RangeActi9
Product nameActi9 iC60
Product or component typeMiniature circuit-breaker
Device short nameiC60H
Device applicationDistribution
Poles description1P
Number of protected poles1
[In] rated current2 A
Network typeDC; AC
Trip unit technologyThermal-magnetic
Curve codeC
Utilisation categoryCategory A conforming to EN/IEC 60947-2
Suitability for isolationYes conforming to EN/IEC 60898-1; Yes conforming to EN/IEC 60947-2
StandardsEN/IEC 60947-2; EN/IEC 60898-1
Network frequency50/60 Hz
[Ue] rated operational voltage12...60 V AC 50/60 Hz; 100...133 V AC 50/60 Hz; 220...240 V AC 50/60 Hz; 12...60 V DC; 60...72 V DC
Magnetic tripping limit8 x In +/- 20 %
Breaking capacity70 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2; 70 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2; 70 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2; 20 kA Icu at 12...60 V DC conforming to EN/IEC 60947-2; 15 kA Icu at 60...72 V DC conforming to EN/IEC 60947-2; 10000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
[Ics] rated service breaking capacity70 kA 100 % x Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2; 70 kA 100 % x Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2; 70 kA 100 % x Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2; 20 kA 100 % x Icu at 12...60 V DC conforming to EN/IEC 60947-2; 15 kA 100 % x Icu at 60...72 V DC conforming to EN/IEC 60947-2
Limitation class3 conforming to EN/IEC 60898-1
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to EN/IEC 60947-2
Contact position indicatorYes
Control typeToggle
Local signallingTrip indicator
mounting modeClip-on; Removable comb busbar installed
Mounting support35 mm DIN rail
Connection pitch18 mm between devices
9 mm pitches2
Height91 mm
Width18 mm
Depth78.5 mm
Product weight0.125 kg
ColourWhite
Mechanical durability20000 cycles
Electrical durability10000 cycles
Connections - terminalsDouble terminal (top or bottom) , for 1 cable(s) , 1…25 mm², rigid, copper; Double terminal (top or bottom) , for 1 cable(s) , 1…16 mm², flexible, copper; Double terminal (top or bottom) , for 1 cable(s) , 1…16 mm², flexible with ferrule, copper; Double terminal (top or bottom) , for 1.0 cable(s) , flexible, copper or aluminium, with ring terminal and accessory
Wire stripping length14 mm for top or bottom connection
Tightening torque2 N.m top or bottom
Earth-leakage protectionWithout
IP degree of protectionIP20 conforming to IEC 60529; IP40 in modular enclosure (Insulation class II) conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Overvoltage categoryIV
Tropicalisation2 conforming to IEC 60068-1
Relative humidity95 % at 55 °C
Ambient air temperature for operation-35…70 °C
Ambient air temperature for storage-40…85 °C
Warranty (in months)18

Properties

Primary standardIEC/EN 60898-1
MOQ1

Standards

Cross-References

Attached Documents