| Manufacturer part number (MPN) | A9F06113 |
| EAN / GTIN | 3606480437809 |
| Product type | Acti9 iC60H miniature circuit breaker (MCB) |
| Poles | 1P |
| Rated current In | 13 A |
| Tripping curve | type B (magnetic trip 4 x In (±20%)) |
| Rated operational voltage Ue | 230/400 V AC, 50/60 Hz |
| Rated breaking capacity Icn | 10 000 A (IEC/EN 60898-1); Icu 15 kA (IEC/EN 60947-2, 400 V) |
| Rated insulation voltage Ui | 500 V |
| Rated impulse withstand voltage Uimp | 6 kV |
| Endurance | 20 000 mechanical / 10 000 electrical operations |
| Degree of protection | IP20 (terminals); IP40 in modular enclosure |
| Operating temperature | -25 °C to +70 °C |
| Mounting | 35 mm DIN rail (clip-on) |
| Conforms to | IEC/EN 60898-1, IEC/EN 60947-2 |
| HS code | 8536.90 |
| Sales unit | pcs |
| Package quantity | 12 pcs |
| Range | Acti9 |
| Product name | Acti9 iC60 |
| Product or component type | Miniature circuit-breaker |
| Device short name | iC60H |
| Device application | Distribution |
| Poles description | 1P |
| Number of protected poles | 1 |
| [In] rated current | 13 A |
| Network type | DC; AC |
| Trip unit technology | Thermal-magnetic |
| Curve code | B |
| Utilisation category | Category A conforming to EN/IEC 60947-2 |
| Suitability for isolation | Yes conforming to EN/IEC 60947-2; Yes conforming to EN/IEC 60898-1 |
| Standards | EN/IEC 60947-2; EN/IEC 60898-1 |
| Network frequency | 50/60 Hz |
| [Ue] rated operational voltage | 12...60 V AC 50/60 Hz; 100...133 V AC 50/60 Hz; 220...240 V AC 50/60 Hz; 12...60 V DC; 60...72 V DC |
| Magnetic tripping limit | 4 x In +/- 20 % |
| Breaking capacity | 42 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2; 30 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2; 15 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2; 20 kA Icu at 12...60 V DC conforming to EN/IEC 60947-2; 15 kA Icu at 60...72 V DC conforming to EN/IEC 60947-2; 10000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1 |
| [Ics] rated service breaking capacity | 21 kA 50 % x Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2; 15 kA 50 % x Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2; 7.5 kA 50 % x Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2; 20 kA 100 % x Icu at 12...60 V DC conforming to EN/IEC 60947-2; 15 kA 100 % x Icu at 60...72 V DC conforming to EN/IEC 60947-2 |
| Limitation class | 3 conforming to EN/IEC 60898-1 |
| [Ui] rated insulation voltage | 500 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to EN/IEC 60947-2 |
| Contact position indicator | Yes |
| Control type | Toggle |
| Local signalling | Trip indicator |
| mounting mode | Clip-on; Removable comb busbar installed |
| Mounting support | 35 mm DIN rail |
| Connection pitch | 18 mm between devices |
| 9 mm pitches | 2 |
| Height | 91 mm |
| Width | 18 mm |
| Depth | 78.5 mm |
| Product weight | 0.125 kg |
| Colour | White |
| Mechanical durability | 20000 cycles |
| Electrical durability | 10000 cycles |
| Connections - terminals | Double terminal (top or bottom) , for 1 cable(s) , 1…25 mm², rigid, copper; Double terminal (top or bottom) , for 1 cable(s) , 1…16 mm², flexible, copper; Double terminal (top or bottom) , for 1 cable(s) , 1…16 mm², flexible with ferrule, copper; Double terminal (top or bottom) , for 1.0 cable(s) , flexible, copper or aluminium, with ring terminal and accessory |
| Wire stripping length | 14 mm for top or bottom connection |
| Tightening torque | 2 N.m top or bottom |
| Earth-leakage protection | Without |
| IP degree of protection | IP20 conforming to IEC 60529; IP40 in modular enclosure (Insulation class II) conforming to IEC 60529 |
| Pollution degree | 3 conforming to EN/IEC 60947-2 |
| Overvoltage category | IV |
| Tropicalisation | 2 conforming to IEC 60068-1 |
| Relative humidity | 95 % at 55 °C |
| Ambient air temperature for operation | -35…70 °C |
| Ambient air temperature for storage | -40…85 °C |
| Warranty (in months) | 18 |