cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Schneider Electric 50437 closed toroid A type, for Vigirex and Vigilhom, TA30, inner diameter 30 mm, rated current 65 A

Schneider Electric · Electrical Components · Current Transformers · France · se.com
Part Number
50437  ·  HS 8536.49
Schneider Electric 50437 closed toroid A type, for Vigirex and Vigilhom, TA30, inner diameter 30 mm, rated current 65 A

Schneider Electric 50437 — closed toroid A type, for Vigirex and Vigilhom, TA30, inner diameter 30 mm, rated current 65 A.

Technical Specifications

Manufacturer part number (MPN)50437
EAN / GTIN3303430504375
Sales unitpcs
Package quantity70 pcs
RangeVigiPacT
Device short nameTA30
Product or component typeEarth leakage current sensor
Device applicationEquipment monitoring and control
Range compatibilityVigiPacT RH10M residual current protection relay; VigiPacT RH10P residual current protection relay; VigiPacT RH21M residual current protection relay; VigiPacT RH21P residual current protection relay; VigiPacT RH68M residual current protection relay; VigiPacT RH86M residual current protection relay; VigiPacT RH86P residual current protection relay; VigiPacT RH99M residual current protection relay; VigiPacT RH99P residual current protection relay; VigiPacT RH197M residual current protection relay; VigiPacT RH197P residual current protection relay; VigiPacT RHU residual current protection relay; VigiPacT RHUs residual current protection relay; VigiPacT RMH residual current protection relay
current sensor typeA type closed toroid
[Ie] rated operational current65 A
Transformer ratio1/1000
Network frequency50/60 Hz; 400 Hz
[Icw] rated short-time withstand current85 kA for 0.5 s
Residual short-circuit withstand current85 kA / 0.5 s conforming to IEC 60947-2
[Ui] rated insulation voltage1000 V
Overvoltage categoryIV
[Uimp] rated impulse withstand voltage12 kV
Mounting modeFixed (plain backplate); Fixed (profiled sheet metal); Fixed (slotted backplate); Clip-on (DIN rail); Clip-on (Vigirex relay)
Calorific value0.98 MJ
Connections - terminalsScrew connection 0.22…2.5 mm²
Diameter29.4 mm inner:
Product weight0.12 kg
Height74.5 mm
Width63 mm
Depth29 mm
IP degree of protectionBody: IP30; Connectors: IP20
Environmental characteristicExposure to damp heat in service: category C2: 48 hours conforming to IEC 60068-2-56; Exposure to damp heat not in service (25...55 °C, PURE WHITE 95 %) : 28 cycles conforming to IEC 60068-2-30; Salt mist: Kb/2 conforming to IEC 60068-2-52
Pollution degreeLevel 3 conforming to IEC 60664-1
Ambient air temperature for operation-35…70 °C
Ambient air temperature for storage-55…85 °C
StandardsIEC 60947-2
Product certificationsCE
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height3.000 cm
Package 1 Width7.000 cm
Package 1 Length15.000 cm
Package 1 Weight108.000 g
Unit Type of Package 2S04
Number of Units in Package 2100
Package 2 Height30.000 cm
Package 2 Width40.000 cm
Package 2 Length60.000 cm
Package 2 Weight11.500 kg
Country of originFR
Warranty (in months)18
ModelSummation current transformer
Rated primary current65 A
Rated secondary current0.065 A
Accuracy class1
CalibratedYes
With contact protectionYes
Opening diameter29.4 mm
Snap mountingYes
With copper railNo
Number of primary inputs4
Secondary connectionPlug-in connection

Properties

MOQ1

Cross-References

Attached Documents