INSULATION MONITOR IT SYSTEM IM20 Modbus (IMD-IM20)

Schneider Electric · Control & Automation · I/O Modules · France · se.com
Part Number
IMD-IM20  ·  HS 9030.39
INSULATION MONITOR IT SYSTEM IM20 Modbus (IMD-IM20)

Schneider Electric IMD-IM20 Isolasjonsoverv. of IT system. Display shows isolasjonsverdi and kapasitans. Pot.fri connector + Modbus.

Technical Specifications

Manufacturer part number (MPN)IMD-IM20
EAN / GTIN3606480321689
Sales unitpcs
Package quantity8 pcs
RangeVigilohm
Device short nameIM20
Product or component typeInsulation monitoring device
Type of IMDAC/DC IMD
Earthing systemIT; HRG
ApplicationMarine and offshore; IT island; Industry; Infrastructure; Power generation; Port, airport, railway
Network sizeMedium
Electrical circuit typePower circuit; Control circuit
Network capacitanceLightly capacitive
Type of network1P + N; 3P; 3P + N
Network rated voltage0…600 V - AC at 45...440 Hz (device connected to neutral) ; 0…480 V - AC at 45...440 Hz (device connected to phase) ; 0…345 V - DC
Alarm threshold settingPre-alarm: 1 kOhm...1 MOhm; Alarm: 0.5...500 kOhm
Type of measurementNetwork insulation resistance, range: 0.1 kOhm...10 MOhm, accuracy: +/- 5 %; Earth leakage capacitance, range: 0.1...60 µF, accuracy: +/- 5 %; History of alarms
Configurable filtering time4 s; 40 s; 160 s
Response time0.8 s 1/5th of set filtering time; 8 s 1/5th of set filtering time; 32 s 1/5th of set filtering time
Time delay range0...5 min for signalling circuit; 0...120 min for alarm
Power quality analysisTransient capture
Input typeContact for injection inhibition Dry contact
Self-testManual; Auto test at start and every 5h
Overvoltage categoryIII
IP degree of protectionFront face: IP52; Rear: IP20
MaterialThermoplastic
Type of installationIndoor
Operating altitude<= 3000 m
Relative humidity0…92 %
Ambient air temperature for operation-25…55 °C
Ambient air temperature for storage-40…70 °C
Pollution degree2
Mounting modeClip-on (DIN rail); Flush-mounted (panel)
Connections - terminalsRemovable screw terminal block 0.2…2.5 mm²
Product weight0.245 kg
Cut-out dimensions92.4 x 92.4 mm
Height110 mm
Width96 mm
Depth59 mm
Display typeLCD display
Information displayedResistance value; Capacitance value; Evolution of resistance in graph
User languageSpanish; English; French; German; Russian; Chinese; Portuguese; Italian
Local signallingGreen indicator light: satisfactory insulation resistance; White indicator light: below prevention threshold; Orange audible and visible alarms: below fault threshold; Orange flashing indicator light: transient fault
Signal contacts composition1 C/O standard or fail-safe
Signalling circuit voltage250 V - AC at 6 A; 48 V - DC at 1 A; 12...24 V - DC at 6 A
Communication port protocolModbus RS485
Communication of dataHMI: test reports; Dry contact: test reports
Fault event logAlarm logs; Time stamping; 30 events
[Us] rated supply voltage110...415 V AC 50/60/400 Hz tolerance: +/- 15 %; 125...250 V DC tolerance: +/- 15 %
Power consumption in VA12 VA
Power consumption in W6 W
Overcurrent protection1 A
StandardsUL 61010-1; IEC 61010-1; IEC 61557-8; IEC 61326-2-4
Product certificationsBV; DNV; CE; EAC; RMRS; EU-RO MR TA; RCM
Environmental characteristicExposure to damp heat not in service conforming to IEC 60068-2-30; Exposure to damp heat in service conforming to IEC 60068-2-56; Salt mist conforming to IEC 60068-2-52; Long-term storage class 1K22 conforming to IEC 60721-3-1; Transport class 2K11 conforming to IEC 60721-3-2; Stationary use at weather protected locations class 3K24 conforming to IEC 60721-3-3
Mechanical robustnessLong-term storage class 1M11 conforming to IEC 60721-3-1; Transport class 2M4 conforming to IEC 60721-3-2; Stationary use class 3M11 conforming to IEC 60721-3-3
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height10.500 cm
Package 1 Width13.500 cm
Package 1 Length16.500 cm
Package 1 Weight453.000 g
Unit Type of Package 2S03
Number of Units in Package 28
Package 2 Height30.000 cm
Package 2 Width30.000 cm
Package 2 Length40.000 cm
Package 2 Weight4.170 kg
Country of originFR
Warranty (in months)18
Operating voltage AC 50 Hz0–600 V
Operating voltage AC 60 Hz0–600 V
Operating voltage DC0–345 V
External power supply requiredNo
Supply voltage AC 50 Hz110–415 V
Supply voltage AC 60 Hz110–415 V
Supply voltage DC125–250 V
Rated operating frequency45–440 Hz
Voltage measuring range0–600 V
Voltage type (operating voltage)AC/DC
Type of electric connectionScrew connection
Voltage type for actuatingAC/DC
With detachable clampsYes
FunctionFor mixed system
Line capacity70 µF
Response value impedance 11–1000 kOhm
Response value impedance 20.5–500 kOhm
Indication of insulation valueYes
Error registration possibleYes
Number of contacts as change-over contact1

Properties

MOQ1

Cross-References