| Manufacturer part number (MPN) | A9A26897 |
| EAN / GTIN | 3606480461613 |
| Sales unit | pcs |
| Package quantity | 12 pcs |
| Voltage | 24 V DC |
| range of product | Acti9 |
| Product or component type | OC and fault contact |
| Device short name | iOF+SD 24 |
| Device application | For Smartlink interface |
| Signal contacts composition | 1 NO + 1 NC |
| [In] rated current | DC-12 2…100 mA at 24 V, DC +/- 20 % |
| 9 mm pitches | 1 |
| Standards | IEC 60947-5-4; IEC 60947-5-1 |
| Quality labels | CE |
| Range compatibility | Acti9 iSW-NA; Acti9 iC60; Acti9 iC65; Acti9 iID; Acti9 ARA; Acti9 RCA; Acti9 iDPN (China version); Acti9 iDPN Vigi; Acti9 connectors Ti24; Acti9 iC40; Acti9 iCVm40; Acti9 iCVr40; Acti9 iDDm40 |
| [Ui] rated insulation voltage | 500 V conforming to IEC 60664-1 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60664-1 |
| Local signalling | Mechanical indicator |
| mounting mode | Clip-on |
| Mounting support | DIN rail |
| Comb busbar and distribution block compatibility | Bottom: YES |
| Height | 88 mm |
| Width | 9 mm |
| Depth | 73.5 mm |
| Product weight | 25 g |
| Colour | White |
| Electrical durability | 20000 cycles conforming to IEC 60947-5-4 |
| Connections - terminals | Spring-loaded terminal Ti24 (top): 2 cable(s) 0.5…1.5 mm² - flexible; Spring-loaded terminal Ti24 (top): 2 cable(s) 0.5…1.5 mm² - rigid |
| Wire stripping length | 10 mm |
| Pollution degree | 2 conforming to IEC 60664-1 |
| Overvoltage category | III |
| Tropicalisation | 2 conforming to IEC 60947-5-1 |
| Relative humidity | 93 % at 40 °C |
| Ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -40…85 °C |
| Number of Units in Package 1 | 1 |
| Number of Units in Package 2 | 12 |
| Number of Units in Package 3 | 120 |
| Warranty (in months) | 18 |
| Function | Auxiliary switch/fault-signal switch |
| Voltage type | DC |
| Rated voltage | 24 V |
| Installed at the factory | No |
| Width in number of modular spacings | 0.5 |
| Rated switch current | 0.1 A |
| Number of fault-signal switches | 1 |
| Device fitting | Earth leakage circuit breaker and miniature circuit breaker (MCB) |
| Additional equipment | Auxiliary switch/fault-signal switch |
| Voltage type for actuating | DC |
| Number of contacts as normally closed contact | 1 |
| Number of contacts as normally open contact | 1 |
| With auto test for earth leakage function | No |
| Suitable for max. number of poles main contact unit (total) | 4 |
| Suitable for max. current main contact unit | 63 A |
| Country of origin | India |