cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Schneider Electric NG125 - circuit breaker - NG125L - 3P - 25A - C curve 18802

Schneider Electric · Electrical Components · Miniature Circuit Breakers · France · se.com
Part Number
18802  ·  HS 8536.20
Schneider Electric NG125 - circuit breaker - NG125L - 3P - 25A - C curve 18802

Schneider Electric 18802 NG125L/C 25-3 Modular power switch

Technical Specifications

Manufacturer part number (MPN)18802
EAN / GTIN3303430188025
Sales unitpcs
Package quantity18 pcs
RangeActi9
Product nameActi9 NG125
Product or component typeMiniature circuit-breaker
Device short nameNG125L
Device applicationDistribution
Poles description3P
Number of protected poles3
[In] rated current25 A at 40 °C
Network typeDC; AC
Trip unit technologyThermal-magnetic
Curve codeC
Breaking capacity100 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2; 40 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2; 50 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2; 15 kA Icu at 500 V AC 50/60 Hz conforming to EN/IEC 60947-2; 36 kA Icu at <= 375 V DC conforming to EN/IEC 60947-2
Utilisation categoryCategory A conforming to IEC 60947-2
Suitability for isolationYes conforming to IEC 60947-2
StandardsEN/IEC 60947-2
Network frequency50/60 Hz
[Ue] rated operational voltage<= 375 V DC; 380...415 V AC 50/60 Hz; 500 V AC 50/60 Hz; 220...240 V AC 50/60 Hz; 440 V AC 50/60 Hz
Magnetic tripping limit8 x In +/- 20 %
[Ics] rated service breaking capacity75 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz; 37.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz; 30 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz; 11.25 kA 75 % conforming to EN/IEC 60947-2 - 500 V AC 50/60 Hz; 50 kA 100 % conforming to EN/IEC 60947-2 - 375 V DC
[Ui] rated insulation voltage690 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage8 kV conforming to EN/IEC 60947-2
Contact position indicatorYes
Control typeManual tripping test; Toggle
Local signallingON/OFF indication; Trip indicator
mounting modeClip-on
Mounting positionVertical
Mounting support35 mm symmetrical DIN rail
Comb busbar and distribution block compatibilityYES
9 mm pitches9
Height103 mm
Depth81 mm
Width81 mm
Product weight0.72 kg
Mechanical durability20000 cycles
Electrical durability10000 cycles
Provision for padlockingPadlockable
Locking options descriptionIntegrated padlocking
Connections - terminalsTunnel type terminals1.5…50 mm² rigid; Tunnel type terminals1…35 mm² flexible
Wire stripping length20 mm
Tightening torque3.5 N.m
Earth-leakage protectionSeparate block
IP degree of protectionIP20 conforming to IEC 60529
IK degree of protectionIK05 conforming to EN/IEC 62262
Pollution degree3 conforming to IEC 60947-2
Overvoltage categoryIV
Tropicalisation2 conforming to IEC 60068-1
Relative humidity95 % at 55 °C
Operating altitude2000 m
Ambient air temperature for operation-30…70 °C
Ambient air temperature for storage-40…70 °C
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height8.6 cm
Package 1 Width12.4 cm
Package 1 Length12.8 cm
Package 1 Weight741 g
Unit Type of Package 2S03
Number of Units in Package 218
Package 2 Height30 cm
Package 2 Width30 cm
Package 2 Length40 cm
Package 2 Weight13.854 kg
Warranty (in months)18
Power loss2.7 W
Built-in depth47 mm
Release characteristicC
Number of poles (total)3
Rated current25 A
Rated voltage415 V
Rated insulation voltage Ui690 V
Rated impulse withstand voltage Uimp8 kV
Frequency50–60 Hz
Concurrently switching neutral conductorNo
Additional equipment possibleYes
Width in number of modular spacings4.5
Degree of protection (IP)IP20
Ambient temperature during operating-30–70 °C
Connectable conductor cross section multi-wired1–35 mm²
Connectable conductor cross section solid-core1.5–50 mm²
Explosion-proofNo
Flush-mounted installationNo
Country of originFrance

Properties

MOQ1

Cross-References

Attached Documents