cBallast
Industrial Parts Catalog
Datasheet generated 2026-09-08
sales@cballast.com
cballast.com

Schneider Electric Miniature circuit-breaker, ACTI9 NG125N, 3P, 63 A, C curve, 25 kA (IEC 60947-2) 18639

Schneider Electric · France · se.com
Part Number
18639  ·  HS 8536.20
Schneider Electric Miniature circuit-breaker, ACTI9 NG125N, 3P, 63 A, C curve, 25 kA (IEC 60947-2) 18639

Schneider Electric 18639 NG125N/C 63-3 Mod.Effbr.

Technical Specifications

Manufacturer part number (MPN)18639
EAN / GTIN3303430186397
Sales unitpcs
Package quantity18 pcs
RangeActi9
Product nameActi9 NG125
Product or component typeMiniature circuit-breaker
Device short nameNG125N
Device applicationDistribution
Poles description3P
Number of protected poles3
[In] rated current63 A at 40 °C
Network typeAC; DC
Trip unit technologyThermal-magnetic
Curve codeC
Breaking capacity20 kA Icu at <= 375 V DC conforming to EN/IEC 60947-2; 10 kA Icu at 500 V AC 50/60 Hz conforming to EN/IEC 60947-2; 20 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2; 25 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2; 50 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2
Utilisation categoryCategory A conforming to IEC 60947-2
Suitability for isolationYes conforming to IEC 60947-2
StandardsEN/IEC 60947-2
Network frequency50/60 Hz
[Ue] rated operational voltage<= 375 V DC; 380...415 V AC 50/60 Hz; 500 V AC 50/60 Hz; 220...240 V AC 50/60 Hz; 440 V AC 50/60 Hz
Magnetic tripping limit8 x In
[Ics] rated service breaking capacity37.5 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz; 18.75 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz; 15 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz; 7.5 kA 75 % conforming to EN/IEC 60947-2 - 500 V AC 50/60 Hz; 20 kA 100 % conforming to EN/IEC 60947-2 - <= 375 V DC
[Ui] rated insulation voltage690 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage8 kV conforming to EN/IEC 60947-2
Contact position indicatorYes
Control typeToggle; Manual tripping test
Local signallingON/OFF indication; Trip indicator
mounting modeClip-on
Mounting positionVertical
Mounting support35 mm symmetrical DIN rail
Comb busbar and distribution block compatibilityYES
9 mm pitches9
Height103 mm
Depth81 mm
Width81 mm
Product weight0.72 kg
Mechanical durability20000 cycles
Electrical durability10000 cycles
Provision for padlockingPadlockable
Locking options descriptionIntegrated padlocking
Connections - terminalsTunnel type terminals1.5…50 mm² rigid; Tunnel type terminals1…35 mm² flexible
Wire stripping length20 mm
Tightening torque3.5 N.m
Earth-leakage protectionSeparate block
IP degree of protectionIP20 conforming to IEC 60529
IK degree of protectionIK05 conforming to EN/IEC 62262
Pollution degree3 conforming to IEC 60947-2
Overvoltage categoryIV
Tropicalisation2 conforming to IEC 60068-1
Relative humidity95 % at 55 °C
Ambient air temperature for operation-30…70 °C
Ambient air temperature for storage-40…70 °C
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height8.6 cm
Package 1 Width12.1 cm
Package 1 Length12.9 cm
Package 1 Weight758 g
Unit Type of Package 2S03
Number of Units in Package 218
Package 2 Height30 cm
Package 2 Width30 cm
Package 2 Length40 cm
Package 2 Weight14.16 kg
Country of originFR
Warranty (in months)18
Power loss4 W
Built-in depth47 mm
Release characteristicC
Number of poles (total)3
Rated current63 A
Rated voltage400 V
Rated insulation voltage Ui690 V
Rated impulse withstand voltage Uimp8 kV
Frequency50–60 Hz
Concurrently switching neutral conductorNo
Additional equipment possibleYes
Width in number of modular spacings4.5
Degree of protection (IP)IP20
Ambient temperature during operating-30–70 °C
Connectable conductor cross section multi-wired1–35 mm²
Connectable conductor cross section solid-core1.5–50 mm²
Explosion-proofNo
Flush-mounted installationNo

Properties

MOQ1

Cross-References