cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Schneider Electric Active arc fault detection RCBO, ACTI9 Active ICV40N ARC, 1P+N, 25A, C curve, 30MA, type A-SI, 6000A A9TDFC625

Schneider Electric · Electrical Components · RCDs & RCBOs · France · se.com
Part Number
A9TDFC625  ·  HS 8536.90
Schneider Electric Active arc fault detection RCBO, ACTI9 Active ICV40N ARC, 1P+N, 25A, C curve, 30MA, type A-SI, 6000A A9TDFC625

Schneider Electric A9TDFC625 Acti 9 Active - Residual current circuit breaker with overcurrent - 1pol + N - 25A C - 30mA A-SI type - with communication and measurement.

Technical Specifications

Manufacturer part number (MPN)A9TDFC625
EAN / GTIN3606481906656
HS code8536.90
Sales unitpcs
Package quantity24 pcs
Rated current25 A
RangeActi9
Product nameActi9 Active iCV40 ARC
Product or component typeActive arc fault detection RCBO
Device short nameiCV40N ARC
Product specific applicationArc fault detection
StandardsEN/IEC 62606; EN/IEC 61009-1; EN/IEC 60947-2; EN/IEC 61009-2-1
Poles description1P + N
Number of protected poles1
Curve codeC
Breaking capacity codeN
Breaking capacity6000 A Icn at 230 V AC 50 Hz conforming to EN/IEC 61009-2-1; 10 kA Icu at 230 V AC 50 Hz conforming to EN/IEC 60947-2
Rated breaking and making capacityIdm 3000 A at 230 V AC 50 Hz conforming to EN/IEC 61009-2-1
Neutral positionLeft
Network typeAC
Earth-leakage protection time delayInstantaneous
Earth-leakage protection classType A-SI (Super Immunised)
Electrical data recordingDate and time; Maintenance indicators
Concentrator compatibilityEcoStruxure Panel Server Advanced; EcoStruxure Panel Server Entry; EcoStruxure Panel Server Universal
Event managementOvervoltage; Earth leakage; Overload
Type of measurementVoltage; Active power; Current; Power factor
AccuracyVoltage: +/- 2 %; Current: +/- 2 %; Power: +/- 5 %
Suitability for isolationYes
Residual current tripping technologyVoltage independent
Trip unit technologyThermal-magnetic
Earth-leakage protectionIntegrated
[In] rated current25 A
Network frequency50 Hz
[Ue] rated operational voltage230 V AC 50 Hz
Device location in systemOutgoer
Magnetic tripping limit5...10 x In
[Ics] rated service breaking capacity6000 A AC 50 Hz conforming to EN/IEC 61009-2-1; 7.5 kA AC 50 Hz conforming to EN/IEC 60947-2
Limitation class3
[Ui] rated insulation voltage250 V AC 50 Hz between phase and neutral
Threshold tripping voltage275 V for +/- 5 V
[Uimp] rated impulse withstand voltage4 kV
Contact position indicatorYes
Control typeToggle
Local signallingON, OFF, fault trip; LED arc fault diagnostic
mounting modeClip-on
Mounting supportDIN rail
ColourWhite (RAL 9003)
Mechanical durability20000 cycles
Electrical durability20000 cycles 230 V AC 50 Hz
Overvoltage categoryIII
Locking options descriptionPadlocking device
cable entryTop and bottom
Connections - terminalsTunnel type terminal 1…16 mm² rigid; Tunnel type terminal 1…10 mm² flexible
Wire stripping length14 mm
Tightening torque2 N.m
Comb busbar and distribution block compatibilityYES
9 mm pitches4
Height91 mm
Width36 mm
Depth73 mm
Product weight220 g
Total power losses5.487 W
Power losses per pole3.5 W
Power losses on neutral1.991 W
Earth-leakage sensitivity30 mA
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree2 conforming to EN/IEC 62606
TropicalisationSeverity B conforming to IEC 60068-2-30 for 28 d
Relative humidity95 % at 55 °C
Operating altitude2000 m
Ambient air temperature for operation-25…50 °C
Ambient air temperature for storage-40…80 °C
Quality labelsIMQ; AENOR; OVE
Warranty (in months)18

Properties

MOQ1

Cross-References

Attached Documents