| Manufacturer part number (MPN) | A9TYBE240 |
| EAN / GTIN | 3606481906038 |
| HS code | 8536.90 |
| Sales unit | pcs |
| Package quantity | 17 pcs |
| Range of product | Acti9 |
| Product or component type | Active arc fault detection with residual current protection add-on block |
| Product name | Acti9 Active VigiARC iC60 |
| Device short name | VigiARC iC60 |
| Poles description | 2P |
| Neutral position | Left |
| [In] rated current | 40 A |
| Network type | AC |
| Network frequency | 50 Hz |
| [Ue] rated operational voltage | 230 V AC |
| Residual current tripping technology | Voltage independent |
| Earth-leakage sensitivity | 30 mA |
| Earth-leakage protection class | Type A-SI (Super Immunised) |
| Earth-leakage protection time delay | Instantaneous |
| Electrical data recording | Date and time; Maintenance indicators |
| Concentrator compatibility | EcoStruxure Panel Server Advanced; EcoStruxure Panel Server Entry; EcoStruxure Panel Server Universal |
| Event management | Overvoltage; Earth leakage; Overload |
| Type of measurement | Voltage; Active power; Current; Power factor |
| Accuracy | Voltage: +/- 2 %; Current: +/- 2 %; Power: +/- 5 % |
| 9 mm pitches | 2 |
| Device location in system | Outgoer |
| [Ui] rated insulation voltage | 250 V AC |
| Threshold tripping voltage | 275 V for +/- 5 V |
| [Uimp] rated impulse withstand voltage | 4 kV |
| Local signalling | ON, OFF, fault trip; LED arc fault diagnostic |
| mounting mode | Clip-on |
| Mounting support | DIN rail |
| Colour | White (RAL 9003) |
| Mechanical durability | 20000 cycles |
| Electrical durability | 10000 cycles > 25 A; 20000 cycles <= 25 A |
| Connections - terminals | Tunnel type terminals1…10 mm² flexible; Tunnel type terminals1…16 mm² rigid |
| Wire stripping length | 14 mm |
| Tightening torque | 2 N.m |
| Height | 91 mm |
| Width | 54 mm |
| Depth | 73 mm |
| Product weight | 102 g |
| Product compatibility | Single terminal |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Pollution degree | 2 |
| Tropicalisation | Severity B conforming to IEC 60068-2-30 for 28 d |
| Operating altitude | 2000 m |
| Ambient air temperature for operation | -25…40 °C |
| Ambient air temperature for storage | -40…80 °C |
| Standards | EN/IEC 62606; EN/IEC 61009-1; EN/IEC 61009-2-1 |
| Quality labels | IMQ |
| Number of Units in Package 1 | 1 |
| Number of Units in Package 2 | 17 |
| Warranty (in months) | 18 |