Schneider Electric Residual current breaker with overcurrent protection (RCBO), ACTI9 ICV40N, 1P+N, 16A, C curve, 6000A, A-SI type, 30MA A9DF3616

Schneider Electric · Electrical Components · RCDs & RCBOs · France · se.com
Part Number
A9DF3616  ·  HS 8536.90
Schneider Electric Residual current breaker with overcurrent protection (RCBO), ACTI9 ICV40N, 1P+N, 16A, C curve, 6000A, A-SI type, 30MA A9DF3616

Schneider Electric A9DF3616 — Acti9 iC60 RCBO. Residual current circuit breaker with overcurrent per IEC 61009, DIN-rail modular. Acti 9 iCV40N RCBO 1PN C 16A 30mA SI.

Technical Specifications

Manufacturer part number (MPN)A9DF3616
EAN / GTIN3606489444396
HS code8536.90
Sales unitpcs
Package quantity6 pcs
Rated current16 A
RangeActi9
Product nameActi9 iCV40
Product or component typeResidual current breaker with overcurrent protection (RCBO)
Device short nameiCV40N
Device applicationDistribution
Poles description1P + N
Number of protected poles1
Neutral positionLeft
[In] rated current16 A
Network typeAC
Network frequency50/60 Hz
Trip unit technologyThermal-magnetic
Curve codeC
Earth-leakage sensitivity30 mA
Suitability for isolationYes conforming to EN/IEC 60947-2
Quality labelsKEMA-KEUR; RCM; EAC; VDE
Device location in systemOutgoer
[Ue] rated operational voltage230 V AC 50/60 Hz
Magnetic tripping limit5...10 x In
Residual current tripping technologyVoltage independent
Earth-leakage protection time delayInstantaneous
Earth-leakage protection classType A-SI (Super Immunised)
Breaking capacity6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 61009-2-1
[Ics] rated service breaking capacity6000 A 100 % x Icn at 230 V AC 50/60 Hz conforming to EN/IEC 61009-2-1
Rated breaking and making capacityIdm 6000 A at 230 V AC 50/60 Hz conforming to EN 61009-2-1; Idm 500 A at 230 V AC 50/60 Hz conforming to IEC 61009-2-1
Limitation class3 conforming to EN/IEC 61009-2-1
[Ui] rated insulation voltage400 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage4 kV
Contact position indicatorYes
Control typeToggle
Local signallingON/OFF indication; Fault indication
mounting modeClip-on
Mounting supportDIN rail
Comb busbar and distribution block compatibilityTop or bottom: tooth
Connection pitch9 mm between phase and neutral
9 mm pitches4
Height85 mm
Width36 mm
Depth73 mm
Product weight210 g
ColourWhite
Mechanical durability20000 cycles
Electrical durability20000 cycles
Locking options descriptionSealable; Padlocking device
Connections - terminalsTunnel type terminals top or bottom 1…16 mm² rigid; Tunnel type terminals top or bottom 1…10 mm² flexible
Wire stripping length14 mm for top or bottom connection
Tightening torque2 N.m top or bottom
Earth-leakage protectionIntegrated
StandardsEN/IEC 61009-2-1
Product certificationsCE
IP degree of protectionIP20 conforming to IEC 60529; IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3
Overvoltage categoryIII conforming to IEC 60364
Electromagnetic compatibility8/20 µs impulse withstand, 3000 A conforming to EN/IEC 61009-2-1
Relative humidity95 % at 55 °C
Operating altitude2000 m
Ambient air temperature for operation-25…60 °C
Ambient air temperature for storage-40…85 °C
Warranty (in months)18

Properties

MOQ1

Cross-References