cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-08
sales@cballast.com
cballast.com

Schneider Electric A9L1H900 ACTI9 IPRD1 25R Replacement Cartridge, Type 1+2, Phase (L-N)

Schneider Electric · Switchgear & Protection · Surge Protectors · France · se.com
Part Number
A9L1H900  ·  HS 8536.90
Schneider Electric A9L1H900 ACTI9 IPRD1 25R Replacement Cartridge, Type 1+2, Phase (L-N)

Schneider Electric A9L1H900 is a replacement plug-in protection cartridge for the Acti9 iPRD1 25r combined Type 1 + Type 2 surge protective device (3P and 3P+N). It restores line-to-neutral (L-N) overvoltage protection after cartridge end-of-life, which the host device signals through its mechanical status window and remote signalling contact. The 18 mm cartridge is replaced from the front without disturbing the installed conductors. Maximum continuous operating voltage Uc 300 V AC. Conforms to IEC 61643-11 / EN 61643-11:2012+A11:2018.

Technical Specifications

Manufacturer part number (MPN)A9L1H900
EAN / GTIN3606486808559
Product typeActi9 iPRD1 25r replacement protection cartridge
Protection modePhase (L-N)
SPD classType 1 + Type 2 (combined)
Compatible host deviceiPRD1 25r, 3P and 3P+N
Max. continuous operating voltage Uc300 V AC
Cartridge width18 mm (1 module)
Mountingfront-plug into iPRD1 base
Conforms toIEC 61643-11:2011, EN 61643-11:2012+A11:2018
HS code8536.90
Sales unitpcs
Package quantity16 pcs
range of productActi9
Product or component typeCartridge
Device short nameiPRD1 25r
Range compatibilityActi9 iPRD1 25r
Surge arrester typeElectrical distribution network
StandardsIEC 61643-11:2011; EN 61643-11:2012; EN 61643-11:2018/A11
Product certificationsCE
Quality labelsVDE
Surge arrester class typeType 1 + 2
Surge arrester technologyMOV + GDT
Product destinationSurge protection device iPRD1 25r 3P; Surge protection device iPRD1 25r 3P + N
Earthing systemTT; TN-S; TN-C
[Ue] rated operational voltage240 V AC 50/60 Hz
Nominal discharge currentDifferential mode: 25 kA (L/N)
Maximum discharge currentDifferential mode: 65 kA L/N
[Iimp] impulse currentDifferential mode: 25 kA L/N 12.5 A.s
[Uc] maximum continuous operating voltageDifferential mode: 300 V L/N
Maximum [Up] voltage protection levelDifferential mode 1.5 kV L/N
[Ut] temporary overvoltage442 V L/N 120 min withstand
Local signallingOperating state: flag (green); Fault indication: flag (red)
mounting modePlug-in
Mounting supportInto SPD module
9 mm pitches4
Height45 mm
Width36 mm
Depth73.5 mm
Product weight165 g
ColourWhite (RAL 9003)
MaterialThermoplastic
Response time< 100 ns
IP degree of protectionIP20
Relative humidity5…95 %
Operating altitude0...4000 m
Ambient air temperature for storage-40…85 °C
Warranty (in months)18

Properties

IP ratingIP20
Primary standardIEC 61643-11
MOQ1

Standards

Cross-References

Attached Documents