cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Schneider Electric Modular surge arrester with pluggable cartridge, ACTI9 IPRD1 12.5, 3P+N, 350V, with remote transfert A9L16482

Schneider Electric · Switchgear & Protection · Surge Protectors · France · se.com
Part Number
A9L16482  ·  HS 8536.30
Schneider Electric Modular surge arrester with pluggable cartridge, ACTI9 IPRD1 12.5, 3P+N, 350V, with remote transfert A9L16482

Schneider Electric A9L16482 Modular surge protection device, Acti9 iPRD1 12.5, 3 P + N, 350 V, with signal contact.

Technical Specifications

Manufacturer part number (MPN)A9L16482
EAN / GTIN3606481490223
Sales unitpcs
Package quantity3 pcs
Number of poles3P+N
Range of productIPRD1
Product nameActi9 iPRD1
Product or component typeSurge arrester with pluggable cartridge
Device short nameiPRD1 12.5
Device applicationDistribution
StandardsEN 61643-11:2012; IEC 61643-11:2011
Quality labelsCE; EAC; VDE
Poles description3P + N
Remote signallingWith
Signal contacts composition1 SD (1 C/O)
Surge arrester typeElectrical distribution network
Earthing systemTT; TN-S
Surge arrester class typeType 1 + 2
Surge arrester technologyMOV + GDT
[Ue] rated operational voltage230/400 V AC (+/- 10 %) at 50/60 Hz
Nominal discharge current20 kA
Maximum discharge current50 kA
[Iimp] impulse currentCommon mode: 50 kA N/PE; Differential mode: 12.5 kA L/N
[Uc] maximum continuous operating voltageDifferential mode: 350 V L/N; Common mode: 255 V N/PE
Maximum [Up] voltage protection level1.5 kV type 1 + 2
Residual current0.003 mA N/PE
[Out] temporary overvoltage337 V L/N 5 s withstand; 1200 V N/PE 200 ms safe failure mode
Disconnector device typeAssociated fuse gG 160 A 120 kA standard; Associated circuit breaker Compact NSX160E 80 A 25 kA standard
Local signallingOperating: mechanical indicator (white); End of life: mechanical indicator (red)
Mounting modeClip-on (DIN rail)
9 mm pitches8
Height89 mm
Width72 mm
Depth69 mm
Product weight619 g
ColourWhite (RAL 9003)
MaterialPA6
Connections - terminalsTunnel type terminal (phase) 10…25 mm² flexible; Tunnel type terminal (phase) 10…35 mm² rigid; Tunnel type terminal (earth) 16…25 mm² flexible; Tunnel type terminal (earth) 16…35 mm² rigid
Wire stripping length14 mm
Tightening torque3.5 N.m
Impulse current12.5 kA
Compatibility codeIPRD1
Market segmentSmall commercial; Residential
IK degree of protectionIK05 conforming to IEC 62262
Pollution degree3
Relative humidity5…95 %
Operating altitude2000 m
Ambient air temperature for operation-25…60 °C
Ambient air temperature for storage-40…80 °C
Number of Units in Package 11
Number of Units in Package 23
Number of Units in Package 39
Warranty (in months)18
Mounting methodDIN rail (top hat rail) 35 mm
Construction size8 modular spacing
Voltage protection level1.5 kV
Max. continuous voltage AC350 V
Nominal voltage AC400 V
Test classType 1 + 2
Voltage protection level L-N1.5 kV
Signalling at the deviceOptical
Degree of protection (IP)IP20
Voltage protection level N-PE1.5 kV
Integrated backup fuseNo
Max. conductor cross section solid (solid, stranded)35 mm²
Max. conductor cross section flexible (fine-strand)25 mm²
System configuration DCNo
System configuration ITNo
System configuration TNNo
System configuration TN-CNo
System configuration TTYes
System configuration otherNo
Voltage switching spark gap technologyNo
Country of originChina

Properties

MOQ1

Cross-References

Attached Documents