cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Schneider Electric Residual current breaker with overcurrent protection (RCBO), ACTI9 IC60, 2P, 16A, C curve, 10000A/15KA, A-SI type, 30MA A9D27216

Schneider Electric · Electrical Components · RCDs & RCBOs · France · se.com
Part Number
A9D27216  ·  HS 8536.90
Schneider Electric Residual current breaker with overcurrent protection (RCBO), ACTI9 IC60, 2P, 16A, C curve, 10000A/15KA, A-SI type, 30MA A9D27216

Schneider Electric A9D27216 — Acti9 iC60 RCBO. Residual current circuit breaker with overcurrent per IEC 61009, DIN-rail modular. Residual current circuit breaker with overcurrent Acti9 IC60 RCBO 2P 16A 30MA C 10kA SI.

Technical Specifications

Manufacturer part number (MPN)A9D27216
EAN / GTIN3606481157430
HS code8536.90
Sales unitpcs
Package quantity36 pcs
Rated current16 A
Number of poles2P
RangeActi9
Product nameActi9 iC60 RCBO
Product or component typeResidual current breaker with overcurrent protection (RCBO)
Device short nameiC60 RCBO
Device applicationDistribution
Poles description2P
Number of protected poles2
[In] rated current16 A
Network typeAC
Network frequency50 Hz
Trip unit technologyThermal-magnetic
Curve codeC
Earth-leakage sensitivity30 mA
Suitability for isolationNo conforming to IEC 60947-1
Quality labelsKEMA-KEUR; NF; IMQ; VDE
Device location in systemOutgoer
[Ue] rated operational voltage220...240 V AC 50 Hz
Magnetic tripping limit5...10 x In
Residual current tripping technologyVoltage independent
Earth-leakage protection time delayInstantaneous
Earth-leakage protection classType A-SI (Super Immunised)
Breaking capacity10000 A Icn at 220...240 V AC 50 Hz conforming to EN/IEC 61009-2-1; 15 kA Icu at 220...240 V AC 50 Hz conforming to EN/IEC 60947-2
[Ics] rated service breaking capacity7500 A 75 % x Icn at 220...240 V AC 50 Hz conforming to EN/IEC 61009-2-1; 7.5 kA 50 % x Icu at 220...240 V AC 50 Hz conforming to EN/IEC 60947-2
Rated breaking and making capacityIdm 6000 A at 220...240 V AC 50 Hz conforming to EN/IEC 61009-2-1
Limitation class3 conforming to EN/IEC 61009-2-1
[Ui] rated insulation voltage500 V AC 50 Hz
[Uimp] rated impulse withstand voltage4 kV
Surge current3000 A
Contact position indicatorNo
Control typeToggle
Local signallingON, OFF, fault trip
mounting modeClip-on
Mounting supportDIN rail
Comb busbar and distribution block compatibilityTop or bottom: YES; Bottom: biconnect
Connection pitch9 mm between poles
9 mm pitches4
Height86 mm
Width36 mm
Depth78 mm
Product weight273 g
ColourWhite
Mechanical durability20000 cycles
Electrical durability10000 cycles
Connections - terminalsTunnel type terminal top or bottom 1…35 mm² rigid; Tunnel type terminal top or bottom 1…25 mm² flexible; Tunnel type terminal top or bottom 1…25 mm² flexible with ferrule
Wire stripping length12 mm for top or bottom connection
Tightening torque2 N.m
Earth-leakage protectionIntegrated
StandardsEN/IEC 60947-2; EN/IEC 61009-2-1
IP degree of protectionIP40 (distribution enclosure) conforming to IEC 60529; IP20 conforming to IEC 60529
Overvoltage categoryIII conforming to IEC 60364
Electromagnetic compatibility8/20 µs impulse withstand, 3000 A conforming to EN/IEC 61009-2-1
Tropicalisation2
Relative humidity95 % at 55 °C
Ambient air temperature for operation-25…60 °C
Ambient air temperature for storage-40…70 °C
Warranty (in months)18

Properties

MOQ1

Cross-References

Attached Documents