cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Schneider Electric IPRD8R modular surge arrester - 3P + N - 350V - with remote transfert A9L08601

Schneider Electric · Switchgear & Protection · Surge Protectors · France · se.com
Part Number
A9L08601  ·  HS 8536.30
Schneider Electric IPRD8R modular surge arrester - 3P + N - 350V - with remote transfert A9L08601

Schneider Electric A9L08601 Acti9 iPRD8r Surge protection device 350V 3P+N.

Technical Specifications

Manufacturer part number (MPN)A9L08601
EAN / GTIN3606480506512
Sales unitpcs
Package quantity3 pcs
Number of poles3P+N
Range of productIPRD
Product nameActi9 iPRD
Product or component typeSurge arrester with pluggable cartridge
Device short nameiPRD8r
Device applicationDistribution
StandardsEN 61643-11:2012; IEC 61643-11:2011
Product certificationsCE
Quality labelsNF; KEMA-KEUR
Poles description3P + N
Remote signallingWith
Signal contacts composition1 SD (1 C/O)
Surge arrester typeElectrical distribution network
Earthing systemTN-S; TT
Surge arrester class typeType 2 + 3
Surge arrester technologyMOV + GDT
[Ue] rated operational voltage230/400 V AC (+/- 10 %) at 50/60 Hz
Nominal discharge currentCommon mode: 2.5 kA (L/PE); Common mode: 2.5 kA (N/PE); Differential mode: 2.5 kA (L/N)
Maximum discharge currentCommon mode: 8 kA L/PE; Common mode: 8 kA N/PE; Differential mode: 8 kA L/N
[Uoc] open circuit voltage10 kV type 3 common mode N/PE; 10 kV type 3 differential mode L/N
[Uc] maximum continuous operating voltageCommon mode: 260 V N/PE; Common mode: 350 V L/PE; Differential mode: 350 V L/N
Maximum [Up] voltage protection levelCommon mode 1.1 kV type 3 N/PE; Differential mode 1 kV type 2 L/N; Differential mode 1.1 kV type 3 L/N; Common mode 1.4 kV type 2 N/PE
[Out] temporary overvoltage337 V L/N 5 s withstand; 1200 V N/PE 200 ms safe failure mode; 442 V L/PE 5 s withstand
Disconnector device typeAssociated circuit breaker iC60L 10 A curve C - Icu 25 kA; Associated circuit breaker IC60N 10 A curve C - Icu 10 kA; Associated circuit breaker iC60H 10 A curve C - Icu 15 kA; Associated fuse gG 25 A - Icu 15 kA; Associated fuse gG 80 A - Icu 50 kA
Signalling circuit voltage0.25 A/250 V AC 50/60 Hz
Mounting modeClip-on (DIN rail)
9 mm pitches8
Height85 mm
Width72 mm
Depth69 mm
Product weight0.421 kg
ColourWhite (RAL 9003)
[Ipe] Ground residual current0.6 mA; 0.003 mA
Connections - terminalsTunnel type terminal (downside) 2.5…35 mm²; Tunnel type terminal (upside) 2.5…35 mm²
Tightening torque2.5 N.m
Compatibility codeIPRD8r
IK degree of protectionIK03 conforming to IEC 62262
Relative humidity5…95 %
Operating altitude2000 m
Ambient air temperature for operation-25…60 °C
Ambient air temperature for storage-40…85 °C
Number of Units in Package 11
Number of Units in Package 23
Number of Units in Package 327
Warranty (in months)18
System configuration DCNo
System configuration ITNo
System configuration TNNo
System configuration TN-CNo
System configuration TTYes
System configuration otherNo
Number of conductors (without earthing)3
Nominal discharge surge current (8/20)2.5 kA
Max. discharge surge current (8/20)8 kA
Short-circuit-proofYes
Nominal voltage AC400 V
Max. continuous voltage AC350 V
Voltage protection level1.4 kV
Voltage protection level L-N1.1 kV
Voltage protection level N-PE1.1 kV
Max. overcurrent protection device, series connection (fuse)80 A
Short-circuit breaking capacity (Isccr)50 kA
Integrated short-circuit protectionNo
Integrated backup fuseNo
Leakage-current freeNo
Mounting methodDIN rail (top hat rail) 35 mm
Construction size4 modular spacing
Max. conductor cross section solid (solid, stranded)25 mm²
Max. conductor cross section flexible (fine-strand)16 mm²
With remote signalling contactYes
Signalling at the deviceOptical
Category type 2Yes
Degree of protection (IP)IP20
Country of originChina

Properties

MOQ1

Cross-References

Attached Documents