Schneider Electric switch disconnector iSW - 4P - 125 A - 415 V A9S65492

Schneider Electric · Switchgear & Protection · Disconnect Switches · France · se.com
Part Number
A9S65492  ·  HS 8536.90
Schneider Electric switch disconnector iSW - 4P - 125 A - 415 V A9S65492

Schneider Electric A9S65492 Load-break switch iSW 4P 125A 415VAC.

Technical Specifications

Manufacturer part number (MPN)A9S65492
EAN / GTIN3606480531194
HS code8536.90
Sales unitpcs
Package quantity3 pcs
Voltage415 V AC
Rated current125 A
Number of poles4P
RangeActi9
Product nameActi9 iSW
Product or component typeSwitch disconnector
Device short nameiSW
Device applicationIsolation; Control
Poles description4P
Utilisation categoryAC-22A
Suitability for isolationYes
[Ie] rated operational current125 A at 415 V AC 50/60 Hz
[Ue] rated operational voltage415 V AC 50/60 Hz
[Icm] rated short-circuit making capacity5 kA switch-disconnector alone
[Icw] rated short-time withstand current1500 A
[Ui] rated insulation voltage500 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage6 kV
Control typeToggle
Local signallingON/OFF indication
Contact position indicatorYes
mounting modeFixed
Mounting supportDIN rail
Comb busbar and distribution block compatibilityTop or bottom: YES
9 mm pitches8
Height85 mm
Width72 mm
Depth73 mm
ColourWhite
Mechanical durability20000 cycles
Electrical durability2500 cycles
Connections - terminalsTunnel type terminals (top or bottom) - <= 1 x 50 mm² - rigid; Tunnel type terminals (top or bottom) - <= 1 x 35 mm² - flexible; Tunnel type terminals (top or bottom) - <= 1 x 35 mm² - flexible with ferrule
Wire stripping length14 mm
Tightening torque3.5 N.m
StandardsIEC 60947-3; EN 60947-3
IP degree of protectionIP20
Pollution degree3
Tropicalisation2
Relative humidity95 % at 55 °C
Ambient air temperature for operation-25…60 °C
Ambient air temperature for storage-40…85 °C
Country of originHU
Warranty (in months)18