Cam switch Of/On 3-Pole 90G bun (K2C003HCH)

Schneider Electric · Switchgear & Protection · Disconnect Switches · France · se.com
Part Number
K2C003HCH  ·  HS 8536.50
Cam switch Of/On 3-Pole 90G bun (K2C003HCH)

Schneider Electric K2C003HCH Cam Switch Of/On 3-pole 90º bottom.

Technical Specifications

Manufacturer part number (MPN)K2C003HCH
EAN / GTIN3389110979633
Sales unitpcs
Package quantity10 pcs
Number of poles3P
Range of productHarmony K
Product or component typeComplete cam switch
Component nameK2
[Ith] conventional free air thermal current20 A
Mounting locationFront
fixing modeØ 22 mm hole
Cam switch head typeWith front plate 45 x 45 mm
Type of operatorBlack handle, length = 35 mm
Rotary handle padlockingWithout
Presentation of legendWith metallic legend, 0 - 1 black marking
Cam switch functionSwitch
ReturnWithout
Off positionWith Off position
Poles description3P
Switching positionsRight: 0° - 90°
IP degree of protectionIP65 conforming to IEC 60529
Switching angle90 °
[Ui] rated insulation voltage690 V (pollution degree 3) conforming to IEC 60947-1
[Ithe] conventional enclosed thermal current16 A
Electrical durability200000 cycles AC-23; 200000 cycles AC-3; 600000 cycles AC-15; 600000 cycles AC-21
Maximum operating rate2.5 cyc/mn AC-21; 2.5 cyc/mn AC-23; 2.5 cyc/mn AC-3; 8.333 cyc/mn AC-15
Short-circuit current10000 A
Short-circuit protection20 A cartridge fuse, type gG
[Uimp] rated impulse withstand voltage4 kV in isolating function; 6 kV conforming to IEC 60947-1
Contact operationSlow-break
positive openingWith
Electrical connectionCaptive screw clamp terminals flexible, clamping capacity: 2 x 1.5 mm²; Captive screw clamp terminals solid, clamping capacity: 1 x 2.5 mm²
Mechanical durability1000000 cycles
CAD overall width45 mm
CAD overall height50 mm
CAD overall depth59 mm
Product weight0.155 kg
StandardsIEC 60947-3 for power circuit; IEC 60947-5-1 for control circuit; CENELEC EN 50013; GB/T 14048.5 for control circuit; GB/T 14048.3 for power circuit
Product certificationsCSA 240 V 3 hp 3 phases 2 -pole(s); UL 240 V 0.33 hp 1 phase 2 -pole(s); CSA 240 V 1 hp 1 phase; UL 240 V 1 hp 3 phases; CCC
Protective treatmentTC
Ambient air temperature for operation-25…55 °C
Ambient air temperature for storage-40…70 °C
Shock resistance30 gn conforming to IEC 68-2-27
Vibration resistance5 gn conforming to IEC 68-2-6 (f = 10…150 Hz)
Overvoltage categoryClass II conforming to IEC 536; Class II conforming to NF C 20-030
Number of Units in Package 11
Number of Units in Package 210
Number of Units in Package 3320
Country of originCZ
Warranty (in months)18
ModelOn/off switch
Rated permanent current Iu20 A
Rated operation current Ie at AC-3, 400 V8 A
With zero (off) positionYes
With retraction in 0-positionNo
Degree of protection (IP), front sideIP65/IP67
Type of electrical connection of main circuitScrew connection
Type of control elementLong rotary handle
Suitable for floor mountingNo
Suitable for front mountingYes
Suitable for distribution board installationNo
Suitable for intermediate mountingYes
Complete device in housingYes

Properties

MOQ1