cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Schneider Electric Vertical distribution length, Canalis KSA800, aluminium, 800A, fixed length 2M, 3 outlets, 3L+N+PE, white RAL9001 KSA800EV4203

Schneider Electric · Electrical Components · Busbar Systems · France · se.com
Part Number
KSA800EV4203  ·  HS 8536.90
Schneider Electric Vertical distribution length, Canalis KSA800, aluminium, 800A, fixed length 2M, 3 outlets, 3L+N+PE, white RAL9001 KSA800EV4203

Schneider Electric KSA800EV4203 Ladders 800A 2M 3 outlet.

Technical Specifications

Manufacturer part number (MPN)KSA800EV4203
EAN / GTIN3606480005596
Sales unitpcs
Rated current800 A
RangeCanalis
Device short nameKSA
Offer typeRising main
Product or component typeBusbar trunking
Busbar descriptionVertical distribution length
Product compatibilityCanalis KSA busbar trunking 500…1000 A
Conductors materialAluminium
Busbar trunking polarity3L + N + PE
Number of tap-off outlets3
[Ie] rated operational current800 A at 35 °C
IP degree of protectionIP55 conforming to IEC 60529
mounting modeBy screws
Dimension typeFix
Length2 m
ColourWhite (RAL 9001)
Number of poles4
Neutral positionRight
Mounting positionVertical
[Ue] rated operational voltage230...690 V
Network frequency50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
[Ui] rated insulation voltage690 V
[Icw] rated short-time withstand current37.4 kA
[Ipk] rated peak withstand current78.7 kA
Electrical connectionLubricated sliding contact
Width113 mm
Height146 mm
Product weight29 kg
Tap-off unit interval500 mm
Radiated magnetic field1.12 µT
Thermal stress limit1758000 kA².s
THDI0…15 % 800 A; 15…33 % 630 A; 33…100 % 500 A
Maximum voltage drop<0.008 V with power factor = 1 at 50 Hz with 1A for 100 m long; <0.009 V with power factor = 0.9 at 50 Hz with 1A for 100 m long; <0.009 V with power factor = 0.8 at 50 Hz with 1A for 100 m long; <0.009 V with power factor = 0.7 at 50 Hz with 1A for 100 m long
StandardsIEC 61439-1; IEC 61439-6
IK degree of protectionIK08 conforming to IEC 62262
Ambient air temperature for operation35 °C (without derating); 55 °C (with derating factor)
Number of Units in Package 11
Warranty (in months)18
Number of conductors (without earthing)4
Rated current AC 50 Hz800 A
Rated voltage AC 50 Hz230–690 V
Number of tap-off units3
Expansion equalizationYes
Fireproof bulkheadNo
RAL-number9001
Degree of protection (IP)IP55
Country of originFrance

Properties

MOQ1

Cross-References