| Manufacturer part number (MPN) | KSA800ED45010 |
| EAN / GTIN | 3606480005541 |
| Sales unit | pcs |
| Rated current | 800 A |
| Range | Canalis |
| Device short name | KSA |
| Offer type | Classic |
| Product or component type | Busbar trunking |
| Busbar description | Horizontal distribution length |
| Product compatibility | Canalis KSA busbar trunking 500…1000 A |
| Conductors material | Aluminium |
| Busbar trunking polarity | 3L + N + PE |
| Number of tap-off outlets | 10 |
| [Ie] rated operational current | 800 A at 35 °C |
| IP degree of protection | IP55 conforming to IEC 60529 |
| mounting mode | By screws |
| Dimension type | Fix |
| Length | 5 m |
| Colour | White (RAL 9001) |
| Number of poles | 4 |
| Neutral position | Up |
| Mounting position | Horizontal |
| [Ue] rated operational voltage | 230...690 V |
| Network frequency | 50/60 Hz |
| [Uimp] rated impulse withstand voltage | 8 kV |
| [Ui] rated insulation voltage | 690 V |
| [Icw] rated short-time withstand current | 37.4 kA |
| [Ipk] rated peak withstand current | 78.7 kA |
| Electrical connection | Lubricated sliding contact |
| Width | 113 mm |
| Height | 146 mm |
| Product weight | 69.2 kg |
| Tap-off unit interval | 1000 mm |
| Radiated magnetic field | 1.12 µT |
| Thermal stress limit | 1758000 kA².s |
| THDI | 0…15 % 800 A; 15…33 % 630 A; 33…100 % 500 A |
| Maximum voltage drop | <0.008 V with power factor = 1 at 50 Hz with 1A for 100 m long; <0.009 V with power factor = 0.9 at 50 Hz with 1A for 100 m long; <0.009 V with power factor = 0.8 at 50 Hz with 1A for 100 m long; <0.009 V with power factor = 0.7 at 50 Hz with 1A for 100 m long |
| Standards | IEC 61439-1; IEC 61439-6 |
| IK degree of protection | IK08 conforming to IEC 62262 |
| Ambient air temperature for operation | 35 °C (without derating); 55 °C (with derating factor) |
| Number of Units in Package 1 | 1 |
| Number of Units in Package 2 | 12 |
| Country of origin | FR |
| Warranty (in months) | 18 |
| Model | Single |
| Flexible | No |
| RAL-number | 9001 |
| Number of conductors (without earthing) | 4 |
| Degree of protection (IP) | IP55 |
| Rated voltage AC 50 Hz | 690 V |
| Number of tap-off units | 10 |
| Rated current AC 50 Hz | 800 A |