RAIL 400A 1,5M 6 Outlet (KSA400ED4156)

Schneider Electric · Electrical Components · Busbar Systems · France · se.com
Part Number
KSA400ED4156  ·  HS 8536.90
RAIL 400A 1,5M 6 Outlet (KSA400ED4156)

Schneider Electric KSA400ED4156 Rail 400A 1,5M 6 outlet.

Technical Specifications

Manufacturer part number (MPN)KSA400ED4156
EAN / GTIN3606480004803
Sales unitpcs
Rated current400 A
RangeCanalis
Device short nameKSA
Offer typeAdvanced
Product or component typeBusbar trunking
Busbar descriptionHorizontal distribution length
Product compatibilityCanalis KSA busbar trunking 400 A
Conductors materialAluminium
Busbar trunking polarity3L + N + PE
Number of tap-off outlets6
[Ie] rated operational current400 A at 35 °C
IP degree of protectionIP55 conforming to IEC 60529
mounting modeBy screws
Dimension typeFix
Length1.5 m
ColourWhite (RAL 9001)
Number of poles4
Neutral positionUp
Mounting positionHorizontal
[Ue] rated operational voltage230...690 V
Network frequency50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
[Ui] rated insulation voltage690 V
[Icw] rated short-time withstand current18.8 kA
[Ipk] rated peak withstand current49.2 kA
Electrical connectionLubricated sliding contact
Width54 mm
Height146 mm
Product weight10.85 kg
Tap-off unit interval500 mm
Radiated magnetic field1 µT
Thermal stress limit354000 kA².s
THDI0…15 % 400 A; 15…33 % 315 A; 33…100 % 250 A
Maximum voltage drop<0.022 V with power factor = 0.9 at 50 Hz with 1A for 100 m long; <0.022 V with power factor = 0.8 at 50 Hz with 1A for 100 m long; <0.021 V with power factor = 0.7 at 50 Hz with 1A for 100 m long; <0.018 V with power factor = 1 at 50 Hz with 1A for 100 m long
StandardsIEC 61439-1; IEC 61439-6
IK degree of protectionIK08 conforming to IEC 62262
Ambient air temperature for operation35 °C (without derating); 55 °C (with derating factor)
Number of Units in Package 11
Country of originFR
Warranty (in months)18
ModelSingle
FlexibleNo
RAL-number9001
Number of conductors (without earthing)4
Degree of protection (IP)IP55
Rated voltage AC 50 Hz230–690 V
Number of tap-off units6
Rated current AC 50 Hz400 A

Properties

MOQ1

Cross-References

Attached Documents