cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

RAIL 160A 5M 20 Outlet (KSA160ED45020)

Schneider Electric · Electrical Components · Busbar Systems · France · se.com
Part Number
KSA160ED45020  ·  HS 8536.90
RAIL 160A 5M 20 Outlet (KSA160ED45020)

Schneider Electric KSA160ED45020 Canalis KSA. Distribution rails 100-1000A.

Technical Specifications

Manufacturer part number (MPN)KSA160ED45020
EAN / GTIN3606480004018
Sales unitpcs
Rated current160 A
RangeCanalis
Device short nameKSA
Offer typeClassic
Product or component typeBusbar trunking
Busbar descriptionHorizontal distribution length
Product compatibilityCanalis KSA busbar trunking 100…250 A
Conductors materialAluminium
Busbar trunking polarity3L + N + PE
Number of tap-off outlets20
[Ie] rated operational current160 A at 35 °C
IP degree of protectionIP55 conforming to IEC 60529
mounting modeBy screws
Dimension typeFix
Length5 m
ColourWhite (RAL 9001)
Number of poles4
Neutral positionUp
Mounting positionHorizontal
[Ue] rated operational voltage230...690 V
Network frequency50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
[Ui] rated insulation voltage690 V
[Icw] rated short-time withstand current4.45 kA
[Ipk] rated peak withstand current22 kA
Electrical connectionLubricated sliding contact
Width54 mm
Height146 mm
Product weight21.4 kg
Tap-off unit interval500 mm
Radiated magnetic field0.41 µT
Thermal stress limit202000 kA².s
THDI0…15 % 160 A; 15…33 % 125 A; 33…100 % 100 A
Maximum voltage drop<0.067 V with power factor = 1 at 50 Hz with 1A for 100 m long; <0.066 V with power factor = 0.9 at 50 Hz with 1A for 100 m long; <0.061 V with power factor = 0.8 at 50 Hz with 1A for 100 m long; <0.056 V with power factor = 0.7 at 50 Hz with 1A for 100 m long
StandardsIEC 61439-1; IEC 61439-6
IK degree of protectionIK08 conforming to IEC 62262
Ambient air temperature for operation35 °C (without derating); 55 °C (with derating factor)
Number of Units in Package 11
Number of Units in Package 220
Country of originFR
Warranty (in months)18
ModelSingle
FlexibleNo
RAL-number9001
Number of conductors (without earthing)4
Degree of protection (IP)IP55
Rated voltage AC 50 Hz230–690 V
Number of tap-off units20
Rated current AC 50 Hz160 A

Properties

MOQ1

Cross-References

Attached Documents