cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Schneider Electric Horizontal distribution length, Canalis KSA160, aluminium, 160A, fixed length 3M, 6 outlets, 3L+N+PE, white RAL9001 KSA160ED4306

Schneider Electric · Electrical Components · Busbar Systems · France · se.com
Part Number
KSA160ED4306  ·  HS 8536.90
Schneider Electric Horizontal distribution length, Canalis KSA160, aluminium, 160A, fixed length 3M, 6 outlets, 3L+N+PE, white RAL9001 KSA160ED4306

Schneider Electric KSA160ED4306 RAIL 160A 3M 6 OUTLET.

Technical Specifications

Manufacturer part number (MPN)KSA160ED4306
EAN / GTIN3606480003998
Sales unitpcs
Rated current160 A
RangeCanalis
Device short nameKSA
Offer typeClassic
Product or component typeBusbar trunking
Busbar descriptionHorizontal distribution length
Product compatibilityCanalis KSA busbar trunking 100…250 A
Conductors materialAluminium
Busbar trunking polarity3L + N + PE
Number of tap-off outlets6
[Ie] rated operational current160 A at 35 °C
IP degree of protectionIP55 conforming to IEC 60529
mounting modeBy screws
Dimension typeFix
Length3 m
ColourWhite (RAL 9001)
Number of poles4
Neutral positionUp
Mounting positionHorizontal
[Ue] rated operational voltage230...690 V
Network frequency50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
[Ui] rated insulation voltage690 V
[Icw] rated short-time withstand current4.45 kA
[Ipk] rated peak withstand current22 kA
Electrical connectionLubricated sliding contact
Width54 mm
Height146 mm
Product weight13.4 kg
Tap-off unit interval1000 mm
Radiated magnetic field0.41 µT
Thermal stress limit202000 kA².s
THDI0…15 % 160 A; 15…33 % 125 A; 33…100 % 100 A
Maximum voltage drop<0.067 V with power factor = 1 at 50 Hz with 1A for 100 m long; <0.066 V with power factor = 0.9 at 50 Hz with 1A for 100 m long; <0.061 V with power factor = 0.8 at 50 Hz with 1A for 100 m long; <0.056 V with power factor = 0.7 at 50 Hz with 1A for 100 m long
StandardsIEC 61439-1; IEC 61439-6
IK degree of protectionIK08 conforming to IEC 62262
Ambient air temperature for operation35 °C (without derating); 55 °C (with derating factor)
Number of Units in Package 11
Number of Units in Package 220
Warranty (in months)18
ModelSingle
FlexibleNo
RAL-number9001
Number of conductors (without earthing)4
Degree of protection (IP)IP55
Rated voltage AC 50 Hz230–690 V
Number of tap-off units6
Rated current AC 50 Hz160 A
Country of originFrance

Properties

MOQ1

Cross-References