cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Schneider Compact NSX100H 3P TMD Trip 100A 70KA

Schneider Electric · Switchgear & Protection · Circuit Breakers · France · se.com
Part Number
LV429550  ·  HS 8536.20
Schneider Compact NSX100H 3P TMD Trip 100A 70KA

Schneider Electric LV429550 Compact NSX100H 3-pole 100A MCCB, TMD thermal-magnetic trip unit. High breaking 70kA at 415V AC per IEC 60947-2. Installed as the primary motor branch-circuit protection device between the incoming feeder and the contactor.

Technical Specifications

SeriesCompact NSX100H
Poles3P
Rated Current100A
Trip UnitTMD thermal-magnetic, fixed
Breaking Capacity Icu70kA at 415V AC
Rated Voltage690V AC max
Frame Size100A
Terminal ConnectionFront, EverLink
MountingPlate, DIN rail (with adapter)
Breaking capacity70 kA
Number of poles3
Rated current100 A
Trip unitTMD
RangeComPact
Product nameComPact NSX
Range of productComPact NSX100...250
Device short nameNSX100B
Product or component typeCircuit breaker
Device applicationDistribution
Protected poles description3t
[In] rated current100 A at 40 °C
[Ue] rated operational voltage690 V AC 50/60 Hz
Network typeAC
Network frequency50/60 Hz
Suitability for isolationYes conforming to EN/IEC 60947-2
Utilisation categoryCategory A
[Icu] rated ultimate short-circuit breaking capacity15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2; 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2; 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2; 40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Performance levelB 25 kA 415 V AC
Trip unit nameTM-D
Trip unit technologyThermal-magnetic
Trip unit protection functionsLI
Control typeToggle
Circuit breaker mounting modeFixed
[Ui] rated insulation voltage800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
[Ics] rated service short-circuit breaking capacity20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2; 25 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2; 40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2; 7.5 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability50000 cycles
Electrical durability10000 cycles at 690 V In; 20000 cycles at 690 V In/2; 30000 cycles at 440 V In; 50000 cycles at 440 V In/2
Mounting supportBackplate
Upside connectionFront
Downside connectionFront
Connection pitch35 mm
Protection typeL : for overload protection (thermal); I : for short-circuit protection (magnetic)
Trip unit rating100 A at 40 °C
Long-time pick-up adjustment type Ir (thermal protection)Adjustable
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Long-time protection delay adjustment type trFixed
[tr] long-time protection delay adjustment range120…400 s at 1.5 x In; 15 s at 6 x Ir
Short-time protection pick-up adjustment type IsdFixed
[Isd] Short-time protection pick-up adjustment range800 A
Short-time protection delay adjustment type tsdFixed
Earth-leakage protectionWithout
Number of slots for electrical auxiliaries5 slot(s)
Width (W)105 mm
Height (H)161 mm
Depth (D)86 mm
Product weight2.05 kg
StandardsEN/IEC 60947
Product certificationsCCC; EAC; Marine
Overvoltage categoryClass II
Electrical shock protection classClass II
Pollution degree3 conforming to IEC 60664-1
IP degree of protectionIP40 conforming to IEC 60529
IK degree of protectionIK07 conforming to IEC 62262
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-50…85 °C
Relative humidity0…95 %
Operating altitude0...2000 m without derating; 2000 m...5000 m with derating
Number of Units in Package 11
Number of Units in Package 212
Country of originFR
Warranty (in months)18
EAN3606480008436

Properties

Primary standardIEC 60947-2; UL 489
MOQ1

Compatibility

NSX100 frame. Compatible with full NSX accessory range: shunt trip MX, undervoltage MN, OF/SD/SDE auxiliary contacts, motor mechanism, Vigi MH.

Standards

Approvals

Attached Documents