| Manufacturer part number (MPN) | 3373100 |
| EAN / GTIN | 4028177495678 |
| Sales unit | pcs |
| Model designation | SK 3373.100 |
| Product type | Air-Water Heat Exchangers |
| Version | wall-mounted; Water-carrying parts copper/brass (Cu/CuZn) |
| Color | RAL 7035 |
| Supply includes | Wired ready for connection; Drilling template; Sealing and assembly components |
| Total cooling output | L 35 W 10 at 400 l/h: 2 kW; L 35 W 10 at 400 l/h: 6,824 BTU/h |
| Rated operating voltage | 230 V, 1~, 50 Hz/60 Hz |
| Rated power Pel | At 50 Hz: 110 W; At 60 Hz: 140 W |
| Permissible operating pressure (p. max.) | 1: 10 bar; 14.5: 145 PSI |
| Duty cycle | 100 % |
| Cooling medium | Water (see Internet for specifications) |
| Water inlet temperature | 1 °C...30 °C; 34 °F...86 °F |
| Water connections | ½" connector sleeve; G ⅜" external thread |
| Temperature control | Basic controller (factory setting +35 °C) |
| Operating temperature range | 1 °C...70 °C; 34 °F...158 °F |
| Dimensions | Width: 400 mm; Height: 950 mm; Depth: 145 mm |
| Setting range | 20 °C...55 °C; 68 °F...131 °F |
| Protection category IP to EN 60 529 | IP 55 |
| Protection category NEMA | UL Type 1; UL Type 3R; UL Type 12 |
| Packaging unit | 1 pc(s). |
| Net weight | 18.757 kg |
| Gross weight | 19.744 kg |
| Customs tariff number | 84158300 |
| ETIM 9 | EC002515 |
| ETIM 8 | EC002515 |
| ECLASS 8.0 | 27180712 |
| Add-on type | Wall surface mounted |
| Operating voltage AC 50 Hz | 207–253 V |
| Operating voltage AC 60 Hz | 207–253 V |
| Voltage type | AC |
| Nominal cooling performance L35W10 400l/h | 2000 W |
| Country of origin | Italy |