R. STAHL Series 8118 increased-safety (Ex e) junction box, type 8118/131-814, article number 133210. Enclosure in glass-fibre reinforced polyester resin (GRP), dark grey, degree of protection IP66. Equipped with 8 mantle terminals for 10 mm² conductors; cable entries: 6 × M25×1.5 polyamide cable gland (clamping range 7–17 mm) + 4 × M25×1.5 stopping plug. Rated for use in Zones 1, 2, 21 and 22. Enclosure dimensions 145×145×71 mm; weight 0.85 kg; rated operational voltage 0–750 V AC; ambient temperature −40 °C to +55 °C (T5). Certified ATEX II 2 G Ex eb IIC T6/T5 Gb and II 2 D Ex tb IIIC T80 °C/T95 °C Db (PTB 99 ATEX 3103) and IECEx Ex eb IIC T6/T5 Gb (PTB 06.0026), with DNV ship approval. STAHL article 133210.
| Manufacturer | R. STAHL |
| Product type | 8118/131-814 |
| Article number | 133210 |
| Enclosure | Glass-fibre reinforced polyester resin (GRP), dark grey |
| Dimensions (W×H×D) | 145×145×71 mm |
| Weight | 0.85 kg |
| Degree of protection | IP66 (IEC 60529) |
| Terminals | 8 × mantle terminal, 10 mm² |
| Cable entries | 6 × M25×1.5 polyamide cable gland (clamping range 7–17 mm) + 4 × M25×1.5 stopping plug |
| Application zones | 1, 2, 21, 22 |
| ATEX marking (gas) | II 2 G Ex eb IIC T6/T5 Gb |
| ATEX marking (dust) | II 2 D Ex tb IIIC T80 °C/T95 °C Db |
| IECEx marking | Ex eb IIC T6/T5 Gb |
| Certificates | ATEX PTB 99 ATEX 3103, IECEx PTB 06.0026 |
| Ambient temperature | −40 °C to +55 °C (T5) |
| Rated operational voltage | 0–750 V AC |
| Ship approval | DNV |
| Additional certification | Brazil (ULB), India (PESO), Korea (KTL) |
| Flammability | IEC/EN 60695 |
| Number of connection clamps | 8 |
| Max. conductor cross section | 10 mm² |
| Length | 129 mm |
| Width | 145 mm |
| Depth | 71 mm |
| Mounting method | Surface mounted |
| Extension possible | No |
| Number of inlets | 8 |
| Type of inlet | Gland nut |
| Material | Plastic |
| Halogen free | Yes |
| Surface protection | Untreated |
| Colour | Grey |
| With cover | Yes |
| Cover attachment | Screwed |
| With transparent cover | No |
| Sealable | No |
| Rated insulation voltage Ui | 750 V |
| Explosion-tested version | Yes |
| For Ex-zone gas | 1, 2 |
| For Ex-zone dust | 21, 22 |
| Country of origin | Norway |
| Material | Glass-fibre reinforced polyester resin (GRP), dark grey |
| Temperature range | −40 °C to +55 °C (T5) |
| IP rating | IP66 |
| Primary standard | IEC/EN 60079-0, IEC/EN 60079-7 (Ex e), IEC/EN 60079-31 (Ex t), IEC 60529 (IP) |
| MOQ | 1 |