Circuit breaker TM 3X126-200A 40K (HNB126H)

Hager Systemer · Electrical Components · Moulded Case Circuit Breakers
Part Number
HNB126H  ·  HS 8536.90
Circuit breaker TM 3X126-200A 40K (HNB126H)

Hager Systemer HNB126H Circuit breaker, thermal and magnetic switch-off, adjustable 3x126 for 200A (Ir 0,63-0,8-1xIn) Ik 40kA.

Technical Specifications

Manufacturer part number (MPN)HNB126H
EAN / GTIN3250613347765
HS code8536.90
Sales unitpcs
Package quantity6 pcs
Rated permanent current Iu200 A
Number of poles3
Overload release current setting125–200 A
Rated voltage220–440 V
Degree of protection (IP)IP40
Position of connection for main current circuitFront side
Motor drive integratedNo
Type of electrical connection of main circuitScrew connection
Type of control elementWing knob
With switched-off indicatorNo
Rated short-circuit breaking capacity Icu at 400 V, 50 Hz40 kA
Adjustment range undelayed short-circuit release1200–2600 A
Suitable for DIN rail (top hat rail) mountingNo
Integrated earth fault protectionNo
Motor drive optionalYes
Device constructionBuilt-in device fixed built-in technique
DIN rail (top hat rail) mounting optionalYes
Complete device with protection unitYes
Country of originGermany

Properties

MOQ1

Cross-References