Hager BD363N RCD Block — Type A, 3-Pole, 63 A, 30 mA

Hager Systemer · Electrical Components · RCDs & RCBOs
Part Number
BD363N  ·  HS 8536.90
Hager BD363N RCD Block — Type A, 3-Pole, 63 A, 30 mA

The Hager BD363N is a type A RCD block rated 63 A across three poles with a 30 mA residual current setting. An RCD block (a "bloc differentiel") is not a standalone breaker. It bolts onto a matching circuit breaker and adds earth-fault protection to it, so one device provides the overcurrent protection and the other the residual current protection. It must be paired with a compatible breaker of the correct frame and rating — it cannot be used on its own. It is a type A device: it responds to sinusoidal AC residual currents and to pulsating DC residual currents, which is the general-purpose requirement wherever ordinary electronic loads are present. At 30 mA it is rated for the protection of people against electric shock, not merely for fire and equipment protection, which requires a residual setting of 30 mA or less. Nominal voltage 220-400 V; the residual setting and the tripping delay are both fixed. Supplied by cBallast on quote-to-invoice terms; lead time and freight are quoted per RFQ against the destination Incoterm.

Technical Specifications

Manufacturer part number (MPN)BD363N
EAN / GTIN3250611343561
Sales unitpcs
Package quantity18 pcs
Rated current63 A
Number of poles3P
Nominal voltage220–400 V
Nominal current63 A
Rated fault current adjustableNo
Rated fault current0.03 A
Delay adjustableNo
Leakage current typeA
Surge current capacity4.5 kA
Frequency50 Hz
Rated insulation voltage Ui500 V
Rated impulse withstand voltage Uimp4 kV
Connectable conductor cross section solid-core1.5–25 mm²
Connectable conductor cross section multi-wired1.5–16 mm²
Anti-nuisance tripping versionNo
With interlocking deviceYes
Degree of protection (IP)IP20
Ambient temperature during operating-25–40 °C
Country of originFrance
Device typeRCD block (add-on residual current unit for a matching circuit breaker)
Rated residual current (IΔn)30 mA
Residual current typeType A
Protection purposeProtection of people against electric shock
Pairing requirementMust be fitted to a compatible Hager circuit breaker; not a standalone device

Properties

MOQ1

Cross-References

Attached Documents