Function SECAP-25 F Directional Earth Fault Relay — IT Network, Fixed 30 mA / 1 s, Ø25 mm Integral Toroid, without Panel (1661702)

Function · Control & Automation · Relays & Timers
Part Number
1661702  ·  HS 8536.20
Function SECAP-25 F Directional Earth Fault Relay — IT Network, Fixed 30 mA / 1 s, Ø25 mm Integral Toroid, without Panel (1661702)

The SECAP-25 is a DIRECTIONAL earth fault relay with a Ø25 mm summation transformer built into the unit, intended for IT (isolated-neutral) networks. Direction is the point of it. In an IT system every feeder is galvanically connected to every other one and the whole network shares its capacitive leakage to earth, so an ordinary earth-leakage relay watching one feeder also registers faults that belong to somebody else's circuit and raises an alarm nobody can act on. A directional relay resolves which side of itself a fault lies on and responds only to faults within its own installation, which is what makes the alarm mean something and what makes it possible to find the fault instead of merely knowing the network has one. It provides a potential-free normally-open alarm contact and a 12 V output for remote annunciation, which drives the CU-12 indicator panel. This is the F variant: FIXED sensitivity at 30 mA with a 1 second delay, supplied WITHOUT the CU-12 indicator panel. Where the alarm is taken to a control system rather than read on the wall, the panel is not needed; where local indication is wanted, order the CU-12 alongside it or specify the SECAP25FP, which is the same relay supplied with the panel. Manufactured in Spain and supplied under the Function brand. Supplied by cBallast on quote-to-invoice terms; lead time and freight are quoted per RFQ against the destination Incoterm.

Technical Specifications

Manufacturer part number (MPN)1661702
Sales unitpcs
El-nummer (NO)1661702
ETIM classSC001444
Operating voltage AC 50 Hz195–265 V
Operating voltage AC 60 Hz195–265 V
External power supply requiredYes
Supply voltage AC 50 Hz195–265 V
Supply voltage AC 60 Hz195–265 V
Rated operating frequency50–60 Hz
Voltage type (operating voltage)AC
Type of electric connectionScrew connection
Rated control supply voltage AC 50 Hz230 V
Rated control supply voltage AC 60 Hz230 V
Voltage type for actuatingAC
With detachable clampsNo
FunctionFor AC-current system
Rated frequency50–60 Hz
Indication of insulation valueNo
Error registration possibleNo
Number of contacts as normally open contact1
Width70 mm
Height85 mm
Depth70 mm
Country of originSpain
Device typeDirectional earth fault relay with built-in summation transformer
Network typeIT (isolated neutral)
DirectionalYes — responds only to earth faults within its own installation
Sensitivity (IΔn)30 mA, fixed
Tripping delay1 s
Integral toroid apertureØ25 mm
Alarm outputPotential-free normally-open contact, plus 12 V output for remote annunciation
Indicator panelNot included — CU-12 panel available separately
Variant codeF = fixed sensitivity
ModelSECAP-25 F

Properties

MOQ1

Cross-References

Attached Documents