| Manufacturer part number (MPN) | 4709866 |
| Brand | Fluke |
| Category | Tools |
| Measurement function | Alternating current |
| AC ampere range | 3 mA, 30 mA, 300 mA, 3 A, 30 A, 60 A |
| Range selection | mA / A: manual selection 3 mA / 30 mA / 300 mA: automatic selection 3 A / 30 A / 60 A: automatic selection |
| Range / Resolution | 3 mA¹ / 0.001 mA |
| 3 mA – 30 A 60 A | 1% + 5 digits 2% + 5 digits |
| Frequency | 40 Hz to 1 kHz |
| Crest Factor | 3 |
| Display (LCD) | Digital readout: 3300 count |
| Display refresh rate | 4 times / sec |
| Maximum conductor diameter | 40 mm |
| Dimensions | 234 x 101 x 46 mm |
| Weight | 500 g |
| Battery | 2 AA, IEC LR6, NEDA 15A, alkaline |
| Battery life | Expected battery life, without using backlight and spotlight, is more than 150 hours |
| Automatic shut-down | Meter automatically shuts down after 15 minutes of inactivity |
| General safety | IEC 61010-1: Pollution Degree 2 |
| Measurement safety | IEC 61010-2-032: CAT III 600 V / CAT IV 300 V |
| Operating temperature | -10 °C to +50 °C |
| Storage temperature | -40 °C to +60 °C |
| Operating humidity | Non-condensing ( |
| Protection class | IEC 60529: IP30 (jaw closed) |
| Operating altitude | 2000 m |
| Storage altitude | 12000 m |
| Current sensor action category | IEC 61557-13: Class 2, ≤30 A / m |
| IEC 61326-1 | Industrial Electromagnetic Environment |
| CISPR 11 | Group 1 Class B |
| Group 1 | Generated inside the equipment and / or use radio frequency energy associated with conducting the energy for the device's own internal functions is essential. |