cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-08
sales@cballast.com
cballast.com

Fluke 3540 FC Three-Phase Power Monitor and Condition Monitoring Kit

Fluke · Safety & Detection · Tools · USA · fluke.com
Part Number
4948724
Fluke 3540 FC Three-Phase Power Monitor and Condition Monitoring Kit

The Fluke 3540 FC Three-Phase Power Monitor measures critical parameters on three-phase systems and wirelessly streams data to the Fluke Connect® Cloud. You can access and track data as well as receive alarms to a mobile device or PC through Fluke Connect Condition Monitoring software.

Technical Specifications

Manufacturer part number (MPN)4948724
BrandFluke
CategoryTools
Color LCD display4.3-inch active matrix color TFT, 480 pixels x 272 pixels, resistive touch panel
Warranty 3540 FC and built-in power supply2 years (battery not included)
Warranty Accessories1 year
Calibration cycle2 years
Dimensions (WxHxD 3540 FC19.8 x 16.7 x 5.5 cm (7.8 x 6.6 x 2.2 in)
Dimensions (WxHxD Detachable power supply13.0 x 13.0 x 4.5 cm (5.1 x 5.1 x 1.8 in)
Dimensions (WxHxD 3540 FC with power supply attached19.8 cmx 16.7 x 9 cm (7.8 x 6.6 x 4.0 in)
Weight 3540 FC1.1kg (2.5 lb)
Weight Tamper protectionKensington lock
Operating temperature0 °C to +45 °C (+32 °F to +113 °F)
Storage temperature<20 °C to +60 °C (-4 °C to +140 °F), with battery: -20 °C to +50 °C (-4 °F to +122 °F)
Operating humidity<10 °C (<50 °F) non condensing
Operating altitude2000 m (6,500 ft) (up to 4,000 m derate to 1000 V CAT II/600 V CAT III/300 V CAT IV)
Storage altitude12,000 m (39,000 ft)
IP RatingIEC 60529:IP50, in connected condition with protection caps in place
VibrationMIL-T-28800E, Type 3, Class III, Style B
IEC 61010-1 IEC mains inputOvervoltage Category II, Pollution Degree 2
IEC 61010-1 Voltage terminalsOvervoltage Category IV, Pollution Degree 2
InternationalIEC 61326-1: Industrial
Korea (KCC)Class A Equipment (Industrial Broadcasting & Communication Equipment)
USA (FCC)47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103.
Frequency range2412 MHz to 2462 MHz
Output power<100 mW
Wiring configurations1-Φ, 1-Φ IT, Split-phase, 3-Φ wye, 3-Φ wye IT, 3-Φ wye balanced, 3-Φ delta, 3-Φ Aron/Blondel (2-element delta), 3-Φ delta open leg, 3-Φ high leg delta, 3-Φ delta balanced. Currents only (load studies)
Number of inputs4 (3 phases and neutral)
Maximum input voltage1000 Vrms (1700 Vpk) phase to neutral
Input impedance10 MΩ each phase to neutral
Bandwidth42.5 Hz to 3.5 kHz
Scaling1:1, variable
Current sensor output voltage Clamp500 mVrms / 50 mVrms; CF 2.8
Current sensor output voltage Rogowski coil150 mVrms/15 mVrms at 50 Hz, 180 mVrms/18 mVrms at 60 Hz; CF 4; all at nominal probe range
Bandwidth (-3 dB)42.5 Hz to 3.5 kHz
Resolution16-bit synchronous sampling
Sampling frequency10.24 kHz at 50/60Hz, synchronized to mains frequency
Input signal frequencyMains 50/60 Hz (42.5 to 69 Hz)
Data storageInternal flash memory (not user replaceable)
Memory sizeTypical 1 offline logging session of 1 week with 1 second intervals. The number of possible logging sessions and logging period depends on user requirements.
Measured parametersVoltage, current, frequency, THD V, THD A, power, power factor, fundamental power, DPF
Averaging interval1 s
Total harmonic distortionTHD for voltage and current is calculated on 25 harmonics
VoltageFull cycle RMS (20 ms at 50 Hz, 16.7 ms at 60 HZ)
CurrentHalf cycle RMS (10 ms at 50 Hz, 8.3 ms at 60 Hz)
Power200 ms
USB-AFirmware updates, max. supply current: 120 mA
Supported modesDirect connection and connection to infrastructure
SecurityWPA2-AES with pre-shared key
Voltage rangeNominal 100 V to 500 V (85 V min to 550 V max) using safety plug input
Mains powerNominal 100 V to 240 V (85 V min to 265 V max) using IEC 60320 C7 input
Power consumptionMaximum 50 VA (max. 15 VA when powered using IEC 60320 input)
Standby power<0.3 W only when powered using IEC 60320 input
Efficiency≥68.2 % (in accordance with energy efficiency regulations)
Mains frequency50/60 Hz ±15 %
Battery powerLi-ion 3.7 V, 9.25 Wh, customer-replaceable
On-battery runtimeUp to 4 hr (up to 5.5 hr in energy saving mode)
Charging time<6 hr

Properties

MOQ1

Cross-References

Attached Documents