Fluke 1760TR Basic Three-Phase Power Quality Recorder

Fluke · Safety & Detection · Tools · USA · fluke.com
Part Number
2637629  ·  HS 9030.84
Fluke 1760TR Basic Three-Phase Power Quality Recorder

Power Quality Monitor – Fluke’s three-phase power quality recorder is fully compliant to IEC 61000-4-30 Class-A and is consistent with compliance testing.

Technical Specifications

Manufacturer part number (MPN)2637629
BrandFluke
CategoryTools
Statistical evaluationPower quality statistics according to EN50160 and DISDIP tables like ITIC, CEBEMA, ANSI
Event stripDips, swells and interruptions are detected and stored in the event strip. Also any trigger which fires generates an event added to this strip.
Triggered recordings rmsAggregation time is adjustable between 10 ms (1/2 cycle), 20 ms (1 cycle), 200 ms (10/12 cycles) or 3 sec (150/180 cycles).
Triggered recordings Mains signallingPhases and N-conductor, Voltage and current
Triggered recordings Online modeVariable refresh rate. This feature allows verification of instrument set up and delivers a quick overview of oscilloscope, transients and events.
Intrinsic uncertaintyrefers to reference conditions and is guaranteed for two years
Quality systemdeveloped, manufactured as per ISO 9001: 2000
Environment conditions Operating temp. range0°C to +50°C; 32°F to +122°F
Environment conditions Working temp. range-20°C to +50°C; -4°F to +122°F
Environment conditions Storage temp. range20°C to +60°C; -4°F to 140°F
Environment conditions Reference temperature23°C ± 2 K; 74°F ± 2 K
Environment conditions Climatic classB2 (IEC 654-1), -20°C to +50°C; -4°F to +122°F
Environment conditions Max. operating altitude2000 m: max. 600 V CAT IV1, power supply: 300 V CAT III 5000 m: max 600 V CAT III1, power supply: 300 V CAT II
Reference conditions Environment temp.23°C ± 2 K; 74°F ± 2 K
Reference conditions Power supply230 V ± 10%
Reference conditions Power frequency50 Hz / 60 Hz
Reference conditions Signaldeclared input voltage Udin
Reference conditions Averaging10 minute intervals
HousingInsulated, robust plastics housing
EMC EmissionClass-A as per IEC/EN 61326-1
EMC ImmunityIEC/EN 61326-1
Power supply RangeAC: 83 V to 264 V, 45 to 65 Hz
Power supply SafetyIEC/EN 61010-1 2nd edition
Power supply Power consumptionNIMH, 7.2 V, 2.7 Ah
Power supply DisplayFluke 1760 features LED indicators for the status of the 8 channels, phase sequence, power supply (mains or accumulator), memory usage, time synchronization, and data transfer.
Power supply Power LEDPermanent light: normal power supply from mains
OFFsupply via internal accumulator in case of a power failure.
Channel LEDs3-color LEDs per channel for: Overload condition Under load condition
Data memory2 GB Flash memory depending on model
Memory modelLinear
InterfacesEthernet (100 MB/s), compatible to Windows® 98/ME/NT/2000/XP RS 232, external modem via RS 232
Baud rate for RS 2329600 Baud to 115 kBaud
Dimensions (H x W x D)325 x 300 x 65 mm (2.8 x 11.8 x 2.6 in)
Weightappr. 4.9 kg; 10.8 lbs (without accessories)
Warranty2 years
Calibration interval1 year recommended for Class-A, otherwise 2 years
Range for 50 Hz systems50 Hz ±15% (42.5 Hz to 57.5 Hz)
Range for 60 Hz systems60 Hz ±15% (51 Hz to 69 Hz)
Resolution16 ppm
Sampling frequency for 50 Hz power frequency10.24 kHz, The sampling rate is synchronized to mains frequency.
Uncertainty for frequency measurements< 20 ppm
Uncertainty of internal clock< 1 s/day
Measurement intervalsAggregation of the interval values as per IEC 61000-4-30 Class-A
Min-
Max-valuesHalf cycle, e.g.: 10 ms rms values at 50 Hz
TransientsSample rate 100 kHz to 10 MHz per channel
Harmonicsas per IEC 61000-4-7:2002: 200 ms
Flickeras per EN 61000-4-15:2003: 10 min (Pst), 2 h (Plt)
Number of inputs8 galvanically isolated inputs for voltage and current measurements.
Sensor safetyup to 600 V CAT IV depending on sensor
Basic safety300 V CAT III
Nominal voltage (rms)100 mV
Range (peak value)280 mV
Overload capacity (rms)1000 V, continuously
Voltage rise ratemax. 15 kV/µs
Input resistance1 MΩ
Input capacitance5 pF
Uncertainty at reference conditionsUncertainty including the voltage sensors is in compliance with IEC 61000-4-30 Class-A. All voltage sensors are suitable for DC up to 5 kHz
With Sensor 1000 V0,1% at Udin = 480 V and 600 V P-N
Sensor 600 V0,1% at Udin = 230 V P-N
Intrinsic uncertainty for harmonicsClass I as per EN 61000-4-7:2002
Reference conditions23°C ±2 K < 60% rH; 74°F ±2 K < 60% rH
Temperature drift100 ppm / K
Aging< 0.05% / year
Common mode rejection> 100 dB at 50 Hz
NoiseNoise voltage, input short-circuited: < 40 µV
DC±(0.2% rdg + 0.1% sensor)