Fluke 1625-2 GEO Earth Ground Tester Kit

Fluke · Safety & Detection · Tools · USA · fluke.com
Part Number
4325181  ·  HS 9030.33
Fluke 1625-2 GEO Earth Ground Tester Kit

The Fluke 1625-2 GEO Earth Ground Tester Kit is a unique earth ground tester that can perform all four types of earth ground measurement including stakeless and staked earth ground measurement.

Technical Specifications

Manufacturer part number (MPN)4325181
BrandFluke
CategoryTools
MemoryInternal memory storage up to 1500 records accessible via USB port
Measuring functionInterference voltage and frequency, earthing resistance 3- and 4-pole with/without clip-on current transformer, resistance 2-pole with AC, 2- and 4-pole with DC
Display4 digit (2999 Digit) - 7 segment liquid crystal display, with improved visibility
OperationCentral rotary switch and function keys
Operating temperature-10°C to 50°C (14°F to 122°F)
Storage temperature-30°C to 60°C (-22°F to 140°F)
Temperature coefficient±0.1% of reading/°C 28°C
Type of protectionIP56 for case, IP40 for battery door according to EN60529
Max voltageWarning – socket "clamp" to socket E, ES, S or H
SafetyProtection by double and/or reinforced insulation. Max. 50 V to earth per IEC61010-1. Pollution degree 2
Quality standardDeveloped, designed and manufactured to comply with DIN ISO 9001
External field influenceComplies with DIN 43780 (8/76)
Auxiliary power6 x 1.5 V alkaline (IEC LR6 or type AA)
Battery life spanWith IEC LR6/type AA: typ. 3,000 measurements (RE+RH ≤ 1 kΩ)
Dimensions (W x H x D)250 x 133 x 187 mm (9.75 x 5.25 x 7.35 in)
Weight≤ 1.1 kg (2.43 lb) without accessories 7.6 kg (16.8 lb) incl. accessories and batteries in carrying case
Case materialPolyester
Measuring range1 V to 50 V
Display range0.0 V to 50 V
Resolution0.1 V
Frequency rangeDC/AC 45 Hz to 400 Hz its
Accuracy±(5% of rdg + 5 digit)
Measuring sequenceApprox. 4 measurements/s
Internal resistanceApprox. 1.5 MΩ
Max. overloadUrms = 250 V
Range1 V to 50 V
Measuring methodCurrent and voltage measurement with probe as IEC61557-5
Open circuit voltage20/48 V, AC
Short circuit current250 mA AC
Measuring frequency94, 105, 111, 128 Hz selected manually or automatic. (AFC) 55 Hz in function R1
Noise rejection120 dB (16 2/3 , 50 , 60, 400 Hz)
Reference Conditions or Specified Operating RangeDesignation Code
Intrinsic error Reference conditionsA
Position Reference position ±90°E1
Supply voltage At the limits stated by the manufacturerE2
Temperature 0°C and 35°CE3
Series interference voltage See 4.2 and 4.3E4
0 to 100 x RA but ≤ 50 kΩE5
System frequency 99% to 101% of the nominal frequencyE7
System voltage 85% to 110% of the nominal voltageE8
Operating error B = ±(|A| + 1,15 √E21 E22 E23 E24 E25 E26 )Part 5, 4.3
Operating error±(5% of rdg + 5 digit)
Measuring timeTypical 8 seconds with a fixed frequency 30 sec. max. with AFC and complete cycle of all measuring frequencies
Measuring error of RH and RSTyp. 10% of RE + RS + RH
Max. probe resistance≤ 1 MΩ
Max. auxiliary earth electrode resistance≤ 1 MΩ
RH with Umeas = 48 V< 300 Ω
RH with Umeas = 20 V< 250 Ω
Minimal current in single branch to be measured 0.5 mAWith transformer (1000:1)
Minimal current in single branch to be measured 0.1 mAWith transformer (200:1)
Max. interference current through transformer 3 AWith transformer (1000:1)
Measuring voltage20 V AC, square pulse
Max. interference voltage24 V, with higher voltages measurement will not be started
Formation of measured valueWith 4-pole measurement wires on H, S, ES can be extended without additional error. Resistances > 1 Ω in wire E can cause additional error of 5m Ω/Ω.
Maximum interference voltage≤ 3 V AC or DC, with higher voltages measurement will not be started
Maximum inductivity2 Henry
Maximum overloadUrms = 250 V
Switch positionRA 4-pole (two clamp Stakeless)
Noise current (IEXT)Max. IEXT = 10 A (AC) (RA < 20 Ω)