cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Fluke 1623-2 GEO Earth Ground Resistance Meter

Fluke · Safety & Detection · Tools · USA · fluke.com
Part Number
4325155
Fluke 1623-2 GEO Earth Ground Resistance Meter

Measure earth ground loop resistances using only clamps with Fluke 1623-2 GEO Earth Ground Resistance Meter. Learn More Now!

Technical Specifications

Manufacturer part number (MPN)4325155
BrandFluke
CategoryTools
User interfaceInstant measurement through TURN and START one button concept. The only operating elements are rotary switch and START button
Robust, water and dust resistantInstrument is designed for tough environmental conditions (rubber protective cover, IP56)
MemoryInternal memory storage up to 1500 records accessible via USB port
Operating temperature-10°C to 50°C (14°F to 122°F)
Storage temperature-30°C to 60°C (-22°F to 140°F)
Temperature coefficient±0.1% of reading/°C 28°C
Intrinsic errorRefers to the reference temperature range and is guaranteed for 1 year
Operating errorRefers to the operating temperature range and is guaranteed for 1 year
Climatic classC1 (IEC 654-1), -5°C to +45°C (23° to +115° F), 5% to 95% RH
Protective typeIP56 for case, IP40 for battery door according to EN60529
SafetyProtection by double and/or reinforced insulation. max. 50 V to earth
IEC61010-1Pollution degree 2
EMC (emission immunity)IEC61326-1: Portable
Quality systemDeveloped, designed and manufactured according to DIN ISO 9001
External voltageV ext, max = 24 V (DC, AC < 400 Hz), measurement inhibited for higher values
V ext rejection> 120 dB (162⁄3, 50, 60, 400 Hz)
Measuring timeTypical 6 seconds
Max. overload250 V rms (pertains to misuse)
Auxiliary power6 x 1.5 V Alkaline (type AA LR6)
Battery life spanTypical > 3,000 measurements
Dimensions (W x H x D)250 x 133 x 187 mm (9.75 x 5.25 x 7.35 in)
Weight1.1 kg (2.43 lb) including batteries 7.6 kg (16.8 lb) incl. accessories and batteries in carrying case
Switch positionRA 3-pole
Resolution0.001 Ω to 10 Ω
Measuring range0.020 Ω to 19.99 kΩ
Accuracy±(2% rdg + 3 d)
Measuring voltageVm = 48 V AC
Short-circuit current> 50 mA
Measure frequency128 Hz
Probe resistance (RS)Max 100 kΩ
Auxiliary earth electrode resistance (RH)Max 100 kΩ
Additional error from RH and RSRH[kΩ]•••RS[kΩ]/RA[Ω]•••0.2%
Probe resistance (RS + RES)Max 100 kΩ
Noise current (IEXT)Max. IEXT = 10 A (AC) (RA < 20 Ω)

Properties

MOQ1

Cross-References

Attached Documents