| Manufacturer part number (MPN) | 65849 |
| EAN / GTIN | 0095969401203 |
| Sales unit | pcs |
| Manufacturer model | Fluke 355 |
| Current measurement AC 10 Hz to 100 Hz | Range 40 A / 400 A / 1400 AC rms |
| Resolution | 10 mA / 100 mA / 1 A |
| Accuracy | 40 A: 1.5% rdg + 15 digits 400 A: 1.5% rdg + 5 digits 1400 A: 1.5% rdg + 5 digits |
| Trigger level for Inrush | 0.50 A / 5.0 A / 5 A |
| Trigger level for Hz filter OFF | 2.50 A / 2.5 A / 8 A |
| Trigger level for Hz filter ON | 0.50 A / 2.5 A / 8 A |
| Crest Factor (50/60 Hz) | Range 40 A / 400 A / 1400 AC |
| Crest Factor 1 | 2 @ 33 A, 2.4 @ 27 A 2 @ 330 A, 2.4 @ 270 A 2 @ 1000 A, 2.4 @ 833 A |
| Current measurement AC 100.1 Hz to 1 kHz | Range 40 A / 400 A / 1400 AC rms |
| Current measurement DC | Range 40 A / 400 A / 2000 A |
| Voltage measurement DC | Range 4 V / 40 V / 400 V / 1000 V |
| Resistance measurement | Range 400 Ω / 4 kΩ / 40 kΩ / 400 kΩ |
| Continuity beeper | On at ≤ 30 Ω Off at ≥ 100 Ω |
| Frequency measurement | Measurement range 5.0 Hz to 1 kHz |
| Accuracy – 5.0 Hz to 100 Hz | 0.2% + 2 counts |