| Manufacturer part number (MPN) | I30S |
| EAN / GTIN | 0095969345101 |
| Sales unit | pcs |
| Manufacturer model | Fluke I30S |
| Specified current range | 30 mA to 30 A DC, 30 mA to 20 A AC rms |
| Usable current range | 5 mA to 30 A DC, 30 mA to 20 A AC rms |
| Crest factor | 1.4 in |
| Output sensitivity | 100 mV/A |
| Accuracy (at +25°C) | DC ±1 % of reading ±2 mA AC ± 0.5 dB of reading ±2 mA |
| Resolution | ±1 mA |
| Load impedance | > 100 kΩ |
| Conductor position sensitivity | ±1% relative to center reading |
| Frequency range | DC to 100 kHz (-0.5 dB) |
| Phase shift below 1 kHz | < 2° |
| Temperature coefficient | ±0.01% of reading / °C |
| Power supply | 9 V Alkaline, MN1604/PP3, 30 hours, low battery indicator |
| Working voltage (see Safety Standards section) | 300 V AC rms or DC |
| Maximum conductor size | 19 mm diameter |
| Output connection | Safety BNC connector, supplied with safety 4 mm adapter |