| Manufacturer part number (MPN) | ESR5-NOS-31-230VAC |
| EAN / GTIN | 4015081497485 |
| Sales unit | pcs |
| Eaton catalogue number | 153152 |
| Depth | 114.5 mm |
| Height | 99 mm |
| Width | 22.5 mm |
| Weight | 0.177 kg |
| Mounting position | As required |
| Switching capacity | 0.01 W; In accordance with IEC 60947-5-1, Outputs |
| Vibration resistance | 10 - 150 Hz |
| Amplitude | 0.15 mm |
| Acceleration | 2 g, (IEC/EN 60068-2-6) |
| Air pressure | 795 - 1080 hPa (operation) |
| Altitude | Max. 2000 m |
| Ambient operating temperature - max | 55 °C |
| Ambient storage temperature - max | 85 °C |
| Ambient operating temperature - min | -20 °C |
| Ambient storage temperature - min | -40 °C |
| Climatic proofing | Dry heat to IEC 60068-2-2; Cold to EN 60068-2-1; Damp heat, constant, to IEC 60068-2-3 |
| Environmental conditions | Condensation: Non-condensing; Clearance in air and creepage distances according to EN 50178, UL 508, CSA C22.2, No. 14-95 |
| Operating temperature - max | 55 °C |
| Operating temperature - min | -25 °C |
| Relative humidity | < 75 % |
| Static heat dissipation, non-current-dependent Pvs | 5.43 W |
| Inrush current | 0.1 - 6 A |
| Rated control supply voltage (Us) at AC |
| 50 Hz - max | 230 V |
| Rated control supply voltage (Us) at AC |
| Rated control supply voltage (Us) at AC |
| 60 Hz - max | 230 V |
| Rated control supply voltage (Us) at AC |
| 60 Hz - min | 20.4 V |
| Rated insulation voltage (Ui) | 250 V |
| Rated operational voltage | 230 V AC (power supply); 230 V AC; Approx. 24 V DC at input, starting and feedback circuit |
| Short-circuit protection | Fuse 10 A gL/gG (Enable current paths), For output circuits, External; Fuse 6 A gL/gG (Signal current paths), For output circuits, External |
| Short-circuit protection rating | 10A gL/gG, NEOZED (N/O), Output fuse, External, Output data; 6A gL/gG, NEOZED (N/C), Output fuse, External, Output data |
| Electric connection type | Screw connection |
| Features | 6 kV between A1-A2 / logic / enable and signal current paths; Reinforced insulation; 3 Non-delayed enable current paths; Safe insulation; Basic insulation; Automatically/manually monitored start |
| Fitted with | Feedback circuit; Approval for TÜV; Start input; Approval according to UL; Detachable clamps |
| Functions | 1-channel |
| Material | Contacts: silver tin oxide, gold plated (AgSnO2 |
| 0.2 µm Au); Enclosure | Polyamide (PA), not reinforced |
| Connection type | M3 screw terminals |
| Current consumption | 22 mA, DC |
| Degree of protection | Terminals: IP20; Enclosure: IP20; IP20; Installation location: ≥ IP54 |
| Duty factor | 100 % |
| Emitted interference | According to EN 61000-6-4 |
| Interference immunity | According to EN 61000-6-2 |
| LED indicator | Status indication of SmartWire-DT network: Green LED |
| Lifespan, mechanical | 10,000,000 Operations |
| Model | Basic device |
| Mounting method | Top-hat rail fixing (according to IEC/EN 60715, 35 mm); Rail mounting possible |
| Mounting width | 22.5 mm |
| Overvoltage category | III |
| Pollution degree | 2 |
| Power loss | Normally 5.43 W |
| Product category | Electronic safety relays |
| Protection | Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274) |
| Rated impulse withstand voltage (Uimp) | 4000 V AC |
| Recovery time | 1000 ms |
| Safety parameter (EN ISO 13849-1) | PL c, Performance level; 300,000 switching cycles, B10d; Cat. 1, Category |
| Safety parameter (IEC 62061) | Cat. 1, Category; SILCL 1, Safety integrity level claim limit; SIL 1, Safety integrity level, In accordance with IEC 61508; 2.42 x 10-10, PFHd, Probability of failure per hour |
| Stop category (IEC 60204) | 0 |
| Suitable for | Monitoring of emergency-stop circuits; Module used to safely interrupt electrical circuits; Safety relay for monitoring emergency stop and protective door switch; Monitoring of position switches |
| Switching frequency | Max. 0.5 Hz, Input data |
| Type | Emergency stop category 0; emergency switching off Protective door |
| Voltage type | AC |
| Input | ∞ ms, Simultaneity for inputs 1/2 |
| Number of inputs | 1-channel |
| Number of outputs (safety related, delayed) with contact | 0 |
| Number of outputs (safety related, undelayed) with contact | 3 |
| Number of outputs (signaling function, delayed) with contact | 0 |
| Number of outputs (signaling function, undelayed) with contact | 1 |
| Permissible total cable resistance | 50 Ω (input and starting circuits for UN) |
| Pick-up time | 50 ms typ. (K1, K2 - for UN manual operation); 300 ms typ. (at Uₑ in automatic mode); 330 ms typ. (if actuated via A1 or S11/S12); 300 ms typ. (K1, K2 - for UN automatic mode); 50 ms typ. (at Uₑ in manual mode) |
| Quadratic summation current | 72 A² (ITH² = I1² + I2² + I3²) |
| Reset time | 20 ms (on actuation via S11/S12); Normally 150 ms (on actuation via A1) |
| Switching voltage | 250 V |
| Uninterrupted current | 5 A N/C, Limiting continuous current; 6 A N/O, Limiting continuous current |
| Screwdriver size | 2, Terminal screw, Pozidriv screwdriver; 3.5 x 0.6 mm, Terminal screw |
| Stripping length (main cable) | 7 mm |
| Terminal capacity | 24 - 12 AWG, solid or stranded; 2 x (0.2 – 1) mm², solid; 2 x (0.25 – 1) mm², flexible with ferrule; 1 x (0.2 – 2.5) mm², solid; 1 x (0.25 – 2.5) mm², flexible with ferrule |
| Tightening torque | 0.6 Nm, Screw terminals |
| Operating voltage AC 50 Hz | 230 V |
| Operating voltage AC 60 Hz | 230 V |
| Power consumption | 5.43 W |
| Supply voltage AC 50 Hz | 230 V |
| Supply voltage AC 60 Hz | 230 V |
| Rated switch current | 6 A |
| Control voltage 1 | 230 V |
| Control voltage 2 | 230 V |
| Type of control voltage 1 | AC |
| Type of control voltage 2 | AC |
| Suitable for monitoring of position switches | Yes |
| Suitable for monitoring of emergency-stop circuits | Yes |
| Suitable for monitoring of valves | No |
| Suitable for monitoring of tactile sensors | No |
| Suitable for monitoring of magnetic switches | No |
| Suitable for monitoring of proximity switches | No |
| Type of electric connection | Screw connection |
| Suitable for rail mounting | Yes |
| Voltage type for actuating | AC |
| With detachable clamps | Yes |
| Evaluation inputs | 1-channel |
| With start input | Yes |
| With muting function | No |
| With feedback circuit | Yes |
| Number of outputs, safety related, undelayed, with contact | 3 |
| Type of safety according to IEC 61496-1 | None |
| Stop category according to IEC 60204 | 0 |
| Performance level according to EN ISO 13849-1 | Level c |
| SIL according to IEC 61508 | 1 |
| With approval for BG BIA | No |
| With approval according to UL | Yes |
| Country of origin | Germany |