| Manufacturer part number (MPN) | EU5E-SWD-4D2R |
| EAN / GTIN | 4015081161133 |
| HS code | 8536.90 |
| Sales unit | pcs |
| Eaton catalogue number | 116383 |
| Depth | 102 mm |
| Height | 90 mm |
| Width | 35 mm |
| Weight | 0.1 kg |
| Certifications | CSA File No.: 2324643; UL File No.: E29184; IEC/EN 61131-2; UL Category Control No.: NKCR; CSA Class No.: 3211-07; CSA; UL |
| Catalog Notes | uts 250 Vac |
| Constant acceleration | 1 g, 8.4 - 150 Hz, according to IEC/EN 61131-2, Vibrations |
| Constant amplitude | 3,5 mm, 5 - 8.4 Hz, according to IEC/EN 61131-2, Vibrations |
| Drop and topple | 50 mm Drop height, Drop to IEC/EN 60068-2-31 |
| Height of fall (IEC/EN 60068-2-32) - max | 0.3 m |
| Mounting position | As required |
| Shock resistance | 15 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 11 ms, 9 Impacts |
| Air pressure | 795 - 1080 hPa (operation) |
| Ambient operating temperature - max | 55 °C |
| Ambient storage temperature - max | 70 °C |
| Ambient operating temperature - min | -25 °C |
| Ambient storage temperature - min | -40 °C |
| Climatic proofing | Damp heat, constant, to IEC 60068-2-3; Dry heat to IEC 60068-2-2 |
| Environmental conditions | Condensation: prevent with appropriate measures |
| Operating temperature - max | 55 °C |
| Operating temperature - min | -25 °C |
| Relative humidity | 5 - 95 % (non-condensing, IEC/EN 60068-2-30) |
| Connection to SmartWire-DT | Yes |
| Connection type | Connection plug: external device plug SWD4-8SF2-5, SmartWire-DT; Plug, 8-pole, SmartWire-DT; Push in terminals, Supply and I/O sensor |
| Data transfer rate | 250 kBit/s, SmartWire-DT; Setting automatically |
| LED indicator | Status indication of Relay outputs: Yellow LED; Status indication of SmartWire-DT network: Green LED; Status indication of input: Yellow LED |
| Protocol | Other bus systems |
| Station | SmartWire-DT slave, SmartWire-DT network |
| Equipment heat dissipation, current-dependent Pvid | 0 W |
| Heat dissipation capacity Pdiss | 0 W |
| Heat dissipation per pole, current-dependent Pvid | 0 W |
| Rated operational current for specified heat dissipation (In) | 0 A |
| Static heat dissipation, non-current-dependent Pvs | 1 W |
| Input current | 4 mA (at 24 V DC, Digital inputs) |
| Input current at signal 1 | 4 mA |
| Output current | 3 A |
| Power loss | 1 W |
| Short-circuit protection | 4 A gL/gG, Relay outputs, External |
| Supply voltage at DC - max | 28.8 VDC |
| Supply voltage at DC - min | 0 VDC |
| Air discharge | 8 kV, according to IEC 61131-2, level 3, ESD |
| Burst impulse | 1 kV, Signal cable, according to IEC/EN 61131-2, Level 3; 1 kV, SmartWire-DT cable, according to IEC/EN 61131-2, Level 3; 2 kV, Supply cable, according to IEC/EN 61131-2, Level 3 |
| Contact discharge | 4 kV, according to IEC/EN 61131-2, Level 2, ESD |
| Electromagnetic fields | 3 V/m at 1.4 - 2 GHz (according to IEC/EN 61131-2:2008); 10 V/m at 80 - 1000 MHz (according to IEC/EN 61131-2:2008); 1 V/m at 2.0 - 2.7 GHz (according to IEC/EN 61131-2:2008) |
| Radiated RFI | 10 V (IEC/EN 61131-2:2008, Level 3) |
| Radio interference class | Class A (EN 55011) |
| Surge rating | 1 kV, Surge I/O cables, Surge (IEC/EN 61131-2:2008, Level 1), EMC |
| Electric connection type | Flat plug-in connection |
| Features | Fieldbus connection over separate bus coupler possible; Fieldbus connection over separate bus coupler possible |
| Functions | For connection of digital I/O signals |
| Current consumption | 45 mA, SmartWire-DT network |
| Degree of protection | IP20 |
| Lifespan, electrical | 50,000 Operations (at 250 V, AC-1, 4 A); 50,000 Operations (at 250 V, AC-15, 3 A); 200,000 Operations (at 24 V, DC-13, 1 A) |
| Mounting method | Rail mounting possible; Wall mounting/direct mounting; Top-hat rail fixing (according to IEC/EN 60715, 35 mm) |
| Overvoltage category | II |
| Pollution degree | 2 |
| Product category | SmartWire-DT slave |
| Terminal capacity | 0.25 - 1.5 mm² (24 - 16 AWG), flexible with ferrule, Terminal for I/O sensor; 0.2 - 1.5 mm² (AWG 24 - 16), solid, Terminal for I/O sensor |
| Type | Digital modules |
| Voltage type | AC |
| Drop-out time | 2.5 ms |
| Input delay | < 0.2 ms |
| Limit value type 1 | Low: < 5 V DC; High: > 15 V DC |
| Load current | Min. 100 mA (at 12 V DC) |
| Number of inputs (digital) | 4 |
| Number of outputs (digital) | 2 |
| Output | 2 Relay Outputs |
| Pick-up time | 5 ms |
| Contact type | N/O contact, Relay output |
| Explosion safety category for dust | None |
| Explosion safety category for gas | None |
| Potential isolation | Outputs to SmartWire-DT: yes; Inputs for SmartWire-DT: yes; Output to output: no |
| Safe isolation | 230 V AC, According to EN 50178 |